Configuring A Goose Control Block With Iet600 - ABB RELION REC615 Engineering Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

1MRS757809 C
5.4.4.2
REC615 and RER615
Engineering Guide
If a data set has quality attributes, the attributes must be located
after the status value of the same data object.
Data set entries for vertical reporting are selected using the data
object level, and entries for GOOSE using the data attribute or
data object level.
After installation of the connectivity package documentation
add-on, a full list of the available signals with descriptions and
IEC 61850 names is available in PCM600 under the
Documentation menu of the IED node. The document name in
PCM600 is Parameter List.
After defining the data entries for the data sets, configure the GOOSE control block
properties.

Configuring a GOOSE control block with IET600

1.
Select the IED node on the IEDs tab in the navigation pane.
2.
Select the GCB Data tab in the editor pane.
GUID-2371BB88-B680-4B2D-97BE-549B96E0DAD5 V1 EN
Figure 23:
Creating a GOOSE control block
3.
To add a new GOOSE control block, right-click the area containing the existing
GOOSE control blocks and select Insert new row.
Section 5
GOOSE
43