Received Goose Message Handling - ABB RELION REC615 Engineering Manual

Grid automation
Hide thumbs Also See for RELION REC615:
Table of Contents

Advertisement

Section 5
GOOSE
5.6
52
During the protection relay start-up phase, the protection relay
keeps the value of the output VALID as "1" until the
communication is activated. After the communication is
activated, the value of the output VALID is updated by the value
received via the communication.
If the data type does not match with the GOOSERCV function
block, the attribute cell is red.
In Signal Matrix, the received GOOSE data can be directly connected to the
relay application. The GOOSE inputs are shown on the Binary or Analog Inputs
sheets and they can be connected to the application receiver function blocks. The
columns represent publisher data and the rows represent the possible subscriber
input points.
If the data type, for example timestamp, is not supported by the relay application,
the attribute column is red. The quality attribute is automatically incorporated in
the application with the status value, and it is not seen in Signal Matrix.
7.
Save the changes made in Signal Matrix.
8.
Write to the IED.

Received GOOSE message handling

A GOOSE frame is not accepted if the Needs Commission bit is set. When the
protection relay uses IEC 61850 Edition 2, data with the Test quality bit set is accepted
only if the receiving device is also in the test mode. When the relay uses IEC 61850
Edition 1, the Test field in GOOSE message is also used. For more information about
GOOSE quality handling, see the corresponding flowcharts.
When the protection relay uses IEC 61850 Edition 2, a GOOSE frame
is not accepted if the Simulation bit is set.
When the protection relay uses IEC 61850 Edition 2, the Test quality bit is active in
the sender if the relay is set to test mode. When the relay uses IEC 61850 Edition 1, the
Test field in GOOSE message is also set when in test mode.
When the GOOSE sender is in test mode and the GOOSE receiver is not, in Edition 1
mode the GOOSE receiver freezes to its previous valid state, and in Edition 2 mode the
data value is defaulted and the quality set to invalid.
The Test bit is active in the sender if the protection relay is set to test mode.
See the technical manual for more information on the test mode.
1MRS757809 C
REC615 and RER615
Engineering Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion rer615

Table of Contents