3.7.2
Accessory details
3.7.2.1
Steam distribution pipe DV41-.../DV71-...
The steam distribution pipes are selected on the basis of the duct width
(for horizontal installation) or the duct height (for vertical installation) and
the capacity of the steam humidifier.
Important! Always select the longest possible steam distribution pipe (opti
mum humidification distance).
B
Steam distribution pipes for
Nordmann AT4
1)
Type DV41-..
Type DV71-..
41200
41350
71350
41500
71500
41650
71650
41800
71800
411000
711000
411200
711200
711500
711800
712000
712300
712500
Material: CrNi steel
1)
Note: If the humidification distance (see chapter 5.4.2) has to be reduced for
technical reasons, the amount of steam per unit must be divided between
several steam distribution pipes or the steam distribution system Mul-
tiPipe must be used. If this is the case, contact your Nordmann supplier.
L
Length (L) steam
distribution pipe
in mm
2)
200
350
500
650
800
1000
1200
1500
1800
2000
2300
2500
special length on request
2)
Duct width (B)
in mm
210...400
400...600
550...750
700...900
900...1100
1100...1300
1300...1600
1600...2000
2000...2400
2200...2600
2500...2900
2700...3100
19