Replacing the detection electrode
ATTENTION: avoid the ignition and detection electrodes to contact metallic parts (blast tube, head, etc.), otherwise
the boiler's operation would be compromised. Check the electrodes position after any intervention on the combustion
head.
To replace the detection electrode, proceed as follows:
1
remove the combustion head according to the procedure on paragraph "Removing the combustion head";
2
by means of an allen key, loose the fixing screws of the detection electrode ER and replace it;
3
replace the combustion head.

Checking the detection current

To check the detection signal follow the scheme in Fig. 38 or Fig. 39. If the signal is less than the value indicated, check the position of
the detection electrode or detector, the electrical contacts and, if necessary, replace the electrode or the detector.
TERMINAL BOARD MC
Fig. 38: Detection by electrode
CIB UNIGAS - M039177CA
Control box
Siemens LFL1.3..
Siemens LFL1.3..
27
SCALA µA DC
ER
Minimum detection signal
6µA (with electrode)
70µA with UV detector)
Fig. 39: Detection by photocell QRA..
39
ER
TERMINAL BOARD
MC