9. Connect the remaining receive IMs by connecting one send interface (lower
female connector X2) to one receive interface (upper male connector X1) in
each case.
Send IM
Figure 4-19
10.Plug the terminator into the lower female connector of the receive IM in the last
ER of the chain (see Reference Manual , Chapter 7).
S7-400 and M7-400 Programmable Controllers, Installation Manual
C79000-G7076-C424-01
www.gkbpx.com
Receive IM
Connection Between a Send IM and Two Receive IMs
Wiring the S7-400
Receive IM
Terminator
4-45