Removing The Compact Starter From A Level Surface (Screw Fastening) - Siemens Sirius Series System Manual

Compact starter, infeed system, load feeders, motor and soft starters
Hide thumbs Also See for Sirius Series:
Table of Contents

Advertisement

8.2.2

Removing the compact starter from a level surface (screw fastening)

Requirements
● The compact starter must be switched off (actuator set to
● The control and auxiliary conductor terminals must be disconnected.
Procedure
Note
The compact starter can be removed from the wall with the wiring still in place (permanent
wiring), i.e. there is no need to disconnect the main conductor terminal blocks.
Step
1
2
3
4
SIRIUS 3RA6 Compact Starter
System Manual, 02/2008, GWA 4NEB 560 0601-02 DS 02
8.2 Removing the SIRIUS 3RA6 compact starter and AS-i mounting module
DANGER
Danger, high voltage!
If removing the compact starter when the system is live, you must remember to set the
actuator to the
OFF position first, otherwise the compact starter could get damaged
and you could get an electric shock.
Instructions
Use a screwdriver to release the top
main conductor terminal block.
Tilt the compact starter forwards so that
there is no risk of it snapping back into
the main conductor terminal block.
Use a screwdriver to release the bottom
main conductor terminal block.
Tilt the compact starter upwards and
pull it forwards in order to remove it
from the main conductor terminal
blocks.
OFF position).
Image
1
1
2
4
4
3
Installation/Removal
65