SPECIFICATIONS

Property
Electrical
24V supply
Quiescent current of unit in power failure
Wire Size Range
Communication
Max number of units on the network
Cabling
Mechanical
Size
Display
Construction
Cable Entry
Finish
Color
Weight
Environmental
Temperature Range
Relative Humidity
Hochiki America Corporation
FireNET L@titude Network Vision Annunciator Information
Guide
Description
21 to 30 VDC
253mA typical (buzzer off @ 24V DC)
301mA typical (buzzer on @ 24V DC)
341mA max (buzzer on @ 21V DC)
14 - 18 AWG
31 annunciators
RS-485 two-wire. Maximum distance from fire control panel: 3900 feet (1200
meters). Specify Belden 9271, 9860, or any 18 - 22 AWG insulated copper-
wire.
9.25" x 6.7" x 2.2" (235 mm x 170 mm x 55 mm)
Full color 800 x 480 LCD with resistive touch screen and automatic backlight
dimming
18 SWG, 1.2mm mild sheet steel, IP30 rated
2 x 20 mm knockouts on top & bottom
4 x 20 mm and 2 x 28 mm knockouts in back
Epoxy powder coated
Red (RAL3002)
Gray (BS 00 A 05)
Black (RAL9005)
4.4 lbs (2 kg) maximum
23°F (-5°C) - 120°F (49°C)
Up to 95%, non-condensing