Advertisement

4 Commissioning [installer]
4.4

Setting the solar installation (only for standard solar pumps)

Observe the specifications of the collector manufacturer for the correct adjustment of the
flow rate.
Reading edge =
Round edge of the float
Example:
about 4 l/min
Three speed solar pump
Optional controllers:
DeltaSol BS/2 (Standard controller)
DelatSol M (Advanced controller)
The commissioning of the solar installation is now complete. Please fill in completely the
commissioning report on page 25.
0DNO0201
1. Set the pump P1 to Max. in the manual mode of
the controller to set the maximum flow rate. The
controller sets the corresponding rotation speed.
If necessary, the flow rate can be adjusted at the
ball valve [3.1].
2. Mount the insulating front shell to the station.
3. Switch the controller to automatic mode
(see controller instructions).
Installation-Operation ST1 Solar Pump Station
Scale DN 20:
3 – 22 l/min
17