Function Check Valves [Installer] - Hamworthy Trigon ST1 Installation, Commissioning, Operation & Service Instructions

Solar pump station
Table of Contents

Advertisement

8 Function check valves [installer]

Within their application range, the check valves in this station prevent unwanted gravity
circulation. The efficiency of the check valves depends on:
the installation height
the temperature difference between the storage tank and the collector
the type of heat transfer medium
In the diagram below you can see whether the check valves integrated in the station are
sufficient. If the check valves are not sufficient, you need to install additional components to
prevent gravity circulation. You can mount components such as syphons ("heat traps"), 2-way
valves (zone valves) or additional check valves.
Example:
The station comprises two check valves (2 x 200 mm wc = 400 mm wc).
You use a mixture of water and 40% of propylene glycol as a solar fluid.
The installation height between the collector and the storage tank is 10 m.
Result:
The check valves prevent gravity circulation up to a temperature difference of about 62 K.
If the temperature difference between the collector and the tank is larger, the difference in
density of the solar fluid will be so large, that the check valves are pushed open.
22
Circulation
Temperature difference storage tank/collector in K
Installation-Operation ST1 Solar Pump Station
8 Function check valves [installer]
Solar fluid
0DNO0201

Advertisement

Table of Contents
loading

Table of Contents