Completion Of Operations - Panasonic U-16GE2E5 Test Run Manual

Gas heat pump air conditioner 2way multi / w multi
Table of Contents

Advertisement

Checking mode changes
For these checks select a mode that is different from the mode in which the performance checks were
carried out.
Press the HOME (S004) key to display the menu item num-
ber. "    " (Figure 27)
Next, press the UP (S005) or DOWN (S006) key to select
menu item number "    " (Figure 28)
After "    " has been displayed, display the test run/
forced setting display "     ". While in test run/forced
setting display press the SET (S007) key. (Figure 29)
When the SET (S007) key is pressed in the test run/forced
setting, the display changes. Use the UP (S005) or DOWN
(S006) key to select the forced cooling test run mode "   
 " or forced heating test run mode "     ". (Figure 30)
• When in heating mode change to cooling mode
• When in cooling mode change to heating mode
When in the forced test run setting mode, press the SET
(S007) key for longer than 1 second and the mode changes to
cooling (heating) test run. At this stage check the following.
• The thick tubes are hot when heating mode is selected (do
not touch the tubes with your bare hand)
• The thick tubes are cold when cooling mode is selected.
Stopping the test run
Press the HOME (S004) key to display the menu item num-
ber. "    " (Figure 27)
Next, press the UP (S005) or DOWN (S006) key to select
menu item number "    " (Figure 28)
After "    " has been displayed, display test run/forced
setting "     ". In test run/forced setting display press the
SET (S007) key. (Figure 29)
When the SET (S007) key is pressed when the status is test
run/forced setting display, the display changes. Use the UP
(S005) or DOWN (S006) key to select the forced cooling test
run mode "     ", or the forced heating test run mode " 
   ". Then press the SET (S007) key for longer than 1
second. The TEST/WARNING indicator (red LED (D052)
goes off, and the state returns to forced setting selection.
(Figure 30)
If as a result of the above a fault has been detected, carry out an
investigation, correction or improvement in accordance with the separate "Service and Technical Reference Manu-
al Type M1 Series, Troubleshooting."

(2) Completion of operations

Check again that there are no omissions in the test run check list record, or that there are no malfunctioning items.
II - 41
Figure 27
Figure 28
Figure 29
Figure 30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents