Download Print this page

SDC EntryCheck 923 Installation Instructions And Setup Manual page 5

Advertisement

(Typical Programming cont.)
See the following example that sets entry codes 1234 for normal
and 5678 for toggle operation.
Press: 0 1 # 1 2 3 4 # 1 2 3 4 # 1 #
01=Programming Step; 1234=Entry Code; 1=Main Relay
Press: 0 1 # 5 6 7 8 # 5 6 7 8 # 20 #
01=Programming Step; 5678=Entry Code; 20=Auxiliary Relay
Select Door Sense or Inhibit Input
The Sense Input (gray wire) can be programmed for either
DOOR SENSE or INHIBIT.
Press: 1 0 # Input #
Input=0 for Door Sense; =1 for Inhibit
When programmed for DOOR SENSE, if an open condition on
the input occurs before access is granted (with an entry code or
with the request-to-enter input) a FORCED ENTRY output will
occur. If an open condition remains 60 seconds after a relay
activation for access, a DOOR AJAR output will occur. NOTE:
Function 11 and/or 12 must also be enabled to use Door Sense.
When programmed for INHIBIT, a closed condition on the input
will prevent Relay #1 from activating when access is requested
with an entry code. This mode is typically used with an external
timer to disable the access device at certain times.
Select Forced Entry Output
Sets which output activates if the DOOR SENSE input opens
before access is granted. This output is timed and configured
by the relay "On-time".
Press: 1 1 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
Select Door Ajar Output
Sets which output activates if the DOOR SENSE input stays
open 60 seconds after access is granted (door ajar time is
adjustable using Function 25). This output is not timed.
Press: 1 2 # Output #
Output=Output to Activate (0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
0=No Output
P:\INSTALLATION INST\Access Controls\INST-923\INST-923.vsd
toggle
Default: INHIBIT
Default: No Output
Default: No Output
Rev F
05-19
Page 5
Select Keypad Lockout Output
Sets which output activates when the keypad is "locked out" after
too many incorrect entry code attempts. The lockout time is 60
seconds.
Press: 1 3 # Output #
Output=Output to Activate (0-4)
1=Main Relay; 2 = Auxiliary Relay; 3=Output #3; 4=Output #4;
Select Keypad Active Output
Sets which output activates when any keys are pressed. This
output is timed. If toggle mode is selected for the output, the timer
value defaults to 2 seconds.
Press: 1 4 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
Select Alarm Shunt Output
Sets which output activates during the time access is granted.
(Use this output ot shunt alarm contacts attached to the access
door.) This output may be timed or toggled.
Press: 1 5 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
Select Request-to-Exit Output
Sets which output activates when the Request-to-Exit input is
grounded. This output may be timed or toggled.
Press: 1 6 # Output #
Output=Output to Activate(0-4)
1=Main Relay; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
REX input terminates toggle of Main or Aux. Relay
Anti-Tamper Output
Sets which output activates when the Anti Tamper switch on the
back of the keypad is activated.
Press: 17 # Output #
Output=Output to Activate(0-4)
0=No Output; 2=Auxiliary Relay; 3=Output #3; 4=Output #4;
Main Relay On-time
Sets the length of time the Main Relay activates when triggered.
Green LED is on when Main Relay is active.
Press: 2 1 # Seconds #
Seconds=Output time in seconds (0-60)
Auxiliary Relay On-time
Sets the length of time the Auxiliary Relay activates when triggered.
Press: 2 2 # Seconds #
Seconds=Output time in seconds (0-60)
Default: No Output
0=No Output
Default: No Output
0=No Output
Default: No Output
0=No Output
Default: No Output
0=No Output
Default: No Output
Default: 02 Seconds
Default: 02 Seconds

Advertisement

loading

This manual is also suitable for:

923 entrycheck