KEYPAD WIRING

See Fig. 3 for an example of a basic door installation. The keypad is
mounted adjacent to the door. An electric door strike is mounted in the
door jamb to release the door lock. A door contact switch is mounted on
top of the door jamb for detecting when the door is open.
Use the following steps to wire the keypad. Refer to the wiring diagram
shown in Fig. 4 to assist in the wiring.
Note: For lock power, use 18 AWG wire or larger (depending on load).
Use 22 AWG or larger for signal connections. Refer to lock
manufacturer's documentation for lock power requirements.
Output Connection
Install a low-voltage fail-secure electric door strike at the door to be
controlled. Route 2 wires from the door strike to the keypad. Connect an
MOV across the coil wires of the strike. Connect the (+) door strike wire to
the keypad's MAIN RELAY N.O wire (yellow). Connect the other door
strike wire to the keypad's PWR(-) wire (black). Connect the keypad's
MAIN RELAY COM wire (white) to the keypad's PWR(+) wire (red) .
Power Connection
Connect the power supply's output terminals to the keypad's PWR(+) wire
(red) and PWR(-) wire (black). If using a DC supply, observe wiring
polarity. If an AC transformer is being used, polarity does not mater.
Caution: If the unit is AC powered, make sure the secondary of
the system transformer is isolated from earth ground.
Earth Ground
To avoid damage to the unit from static discharges, this unit must be
connected to a proper earth ground. Connect the green earth ground wire
to a good earth grounding point. Suggested wiring size is 18 AWG for
earth ground.
JP2
ANTI-TAMPER
SWITCH
Sense Input
RE
Note: The SENSE input (gray wire) can be programmed as either a
door sense or inhibit input. Both features cannot be used at the same
time. If you are not using the sense input, program this input for inhibit.
Door Sense: (Detect forced entry or door ajar conditions) Install a
normally closed door switch on the door and route two wires from the
switch to the keypad. Connect the door switch to the keypad's SENSE
wire (gray/ E8) and COM wire (any black wire).
Inhibit: (Disable access) If an inhibit switch or timer is going to be used for
temporarily disabling the keypad, route two wires from the switch or timer
to the keypad. Connect the inhibit switch/timer's normally open contacts
to the keypad's SENSE (gray/ E8) and COM (black wires) terminal.
Request-to-Exit Input
(wiring shown on page 3, fig. 4)
If a request-to-exit pushbutton is going to be used, route two wires from
the keypad box to a normally open pushbutton mounted on the secure
side of the door. Connect the wires to the pushbutton and to the keypad's
REX wire (violet/ E6) and COM (black wires) terminals.
Solid State Outputs
The two solid state outputs (Outputs #3 & #4) can be programmed to
activate during various conditions. These "open collector" outputs can be
used to activate indicators or sounders. See fig. 5 for wiring examples
using the solid state outputs.
P:\INSTALLATION INST\Access Controls\INST-923\INST-923.vsd
Grn Wire
To earth ground
MAIN
RELAY
Rev F
05-19
Page 3
2 wires for
power supply
2 wires for
door sensor
earth
ground
923
Keypad
2 wires
for strike
Fig. 3 Basic Door Installation
TO POWER SUPPLY
FAIL SECURE CONNECTION
FAIL SAFE CONNECTION
WIRE PIGTAIL
BLACK
COMMON
PINK/SALMON
{
OUTPUT #4
*
BLUE
OUTPUT #3
BLACK
COMMON
GREEN
NOT USED
VIOLET
REQUEST TO EXIT
BLACK
COMMON
GRAY
SENSE
*
AUXILIARY OUTPUTS
100mA MAX TO COMMON
Fig. 4 Basic Door Installation Wiring
EXAMPLE #1:
OUTPUT #3 LIGHTS AN LED
OUTPUT #4 LIGHTS AN LED AND SOUNDS A BEEPER
+
POWER
SUPPLY
1KΩ
LED
BLUE
OUTPUT #3
PINK/SALMON
OUTPUT #4
EXAMPLE #2:
OUTPUT #3 LIGHTS A LAMP POWERED FROM AN EXTERNAL SOURCE
OUTPUT #4 TRIGGERS A NORMALLY OPEN ALARM PANEL ZONE
BLUE
OUTPUT #3
PINK/SALMON
OUTPUT #4
END OF LINE
RESISTOR
BLACK
OUTPUT #4 COM
BLACK
OUTPUT #3 COM
Fig. 5 Using Solid State Outputs
Door Sensor Switch
Electric Strike
-
BLACK
KEYPAD POWER
}
12 or 24 VOLTS
RED
+
AC OR DC
BLACK
NO
}
AUXILIARY RELAY
WHITE
COM
2 AMPS @ 28VDC
ORANGE
NC
MAX
YELLOW
NO
}
MAIN RELAY
WHITE
COM
5 AMPS @ 28VDC
ORANGE
NC
MAX
REQUEST-TO-EXIT
DOOR POSITION
SWITCH
SWITCH
[N/O]
[N/C]
NC
NO
C
C
NO
+
ELECTRONIC
BEEPER
1KΩ
-
LED
LOW
NO ZONE
VOLTAGE
LAMP
ALARM PANEL
+
POWER
-
COMMON
SOURCE
EACH
OUTPUT
100 mA
MAXIMUM