8.5. Panic Alarm

The EchoView has a "Panic" function, where you can manually trigger the relays at the main
FMC2000 controller in the network. This must be configured in the EchoView in advance. This
function allows you to trigger any individual relay or all relays simultaneously.

8.6. Enabling/Disabling The "Panic Button" Function

Note: By default, the "Panic Button" feature is disabled.
1. Start the EchoView in Diagnostic mode by pressing and holding the [Y/+] and [MODE] keys
simultaneously.
2. Once startup is completed and the main screen is shown, enter Programming mode by
pressing and holding [MODE] and [N/-] simultaneously.
3. Provide the 4-digit password and press [Y/+] to enter it.
Note: The default password is "0000."
This screen appears:
4. Press [N/-] until "Operating Mode" is highlighted.
5. Press [MODE] to select "Operating Mode."
"Panic Enable" or Panic Disable is highlighted.
EchoView User's Guide
or
31