Other Approvals; Emc And Environmental Type Tests - Siemens RUGGEDCOM RS950G Installation Manual

Hide thumbs Also See for RUGGEDCOM RS950G:
Table of Contents

Advertisement

Chapter 6
Certification
Section 6.1.8

Other Approvals

This device meets the requirements of the following additional standards:
• IEEE 1613
IEEE Standard Environmental and Testing Requirements for Communications Networking Devices in Electric
Power Substations
• IEC 61850-3
Communication Networks and Systems in Substations – Part 3: General Requirements
Section 6.2

EMC and Environmental Type Tests

The RUGGEDCOM RS950G has passed the following EMC and environmental tests.
IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
30
Description
ESD
Enclosure Contact
Enclosure Air
Radiated RFI
Enclosure Ports
Burst (Fast Transient)
Signal Ports
DC Line-to-Line
AC Line-to-Line
Earth Ground Ports
Surge
Signal Ports
DC Line-to-Line
AC Line-to-Line
Induced
Signal Ports
(Conducted) RFI
DC Line-to-Line
AC Line-to-Line
Earth Ground Ports
Magnetic Field
Enclosure Ports
Voltage Dips
DC Line-to-Line
and Interrupts
AC Line-to-Line
Test Levels
± 8 kV
± 15 kV
20 V/m
± 4 kV @ 2.5 kHz
± 4 kV
± 4 kV
± 4 kV
± 4 kV Line-to-Ground, ± 2 kV Line-to-Line
± 2 kV Line-to-Ground, ± 1 kV Line-to-Line
± 4 kV Line-to-Ground, ± 2 kV Line-to-Line
10 V
10 V
10 V
10 V
40 A/m continuous, 1000 A/m for 1 s
1000 A/m for 1 s
30% for 0.1 s, 60% for 0.1 s, 100% for 0.05 s
30% for 1 period, 60% for 50 periods
RUGGEDCOM RS950G
Installation Guide
Severity Levels
4
4
RUGGEDCOM-
specified
severity levels.
a
Note
4
4
4
4
3
4
3
3
3
3
RUGGEDCOM-
specified
severity levels.
5
Other Approvals

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents