Cassette panel IR
Corresponds to
receiver digital display
outdoor error
(flashing)
28
2A
2B
2C
2D
2E
2F
30
39
3A
3B
3E
3F
40
41
Note:
The outdoor failure can also be indicated by the indoor unit, the checkin gmethod as followings: If the outdoor error
code is M(DECIMAL), the indoor unit's I.R. receiver display will show the after convert3erd hexadecimal code of
"M+20"(DECIMAL)
For example, if the outdoor error code is 2, the indoor unit I.R. receiver display will flash the error code 16(2→
2+20=22→change decmal 22 to hexadecimal code, get 16)
Large Cassette Error Code Logic
code
20
Indoor pipe temperature too high
22
PFC circuit loop overcurrent
23
Temperature too high for compressor driver module
24
Compressor start failure
25
Input overcurrent of the drive module
26
Lack phase of the drive module power supply
27
Input current sampling circuit fault
28
No wiring of the compressor
Compressor overcurrent detected by
37
compressor driver module
38
Drive module's ambient temp. sensor abnormal
39
Mid-condenser temp. sensor TC abnormal
42
High pressure switch abnormal(open circuit)
43
Low pressure switch abnormal(open circuit)
44
Outdoor condenser temperatureTC too high
45
System low pressure protection
Description of malfunction
72
FlexFit Pro
Remarks
Malfunction of
outdoor unit.
Refer to outdoor unit
troubleshooting
list for more details