1. GENERAL

The gas fired infra-red luminous heaters are suit-
able to be installed for heating of non-residential
indoor or outdoor spaces. These installation in-
structions are intended for the ecoSchwank-
MILLIVOLT / IL-MILLIVOLT heaters. All
installations must conform to the following instal-
lation requirements. All local, provincial and na-
tional code requirements including the current lat-
est edition B149.1 INSTALLATION CODE" in
Canada, and ANSI Z223.1 in the U.S.A. for gas
burning appliances and equipment. The latest edi-
tion Electrical Code PART 1 CSA C22.1 in Can-
ada and ANSI/NFPA N0 70 in the U.S.A. must

2. INSTALLATION REQUIREMENTS

2.1 INSTALLATION IN AIRCRAFT HANGARS

Luminous Heaters are suitable for use in aircraft
hangars when installed in accordance with the fol-
lowing:
A. A minimum clearance of 10 ft above either the
highest fuel storage compartment or the high-
est engine enclosure of the highest aircraft
which may occupy the hangar. The clearance
to the bottom of the heater shall be measured
from the upper surface of either the fuel stor-
age compartment or the engine enclosure,
whichever is higher from the floor.
also be observed. Due to ever changing standards
and requirements, revision to our equipment and
installation procedures may be necessary. In case
of discrepancies, the latest installation manual
will take priority.
The
ecoSchwank-MILLIVOLT
MILLIVOLT heater may be installed for heating
of non-residential indoor spaces. It is beyond the
scope of these instructions to embrace all condi-
tions that will be encountered. All system piping
must be supported in accordance with acceptable
practice, local codes, and applicable standards.
B. A minimum clearance of 8 ft must be main-
tained from the bottom of the heater in other
sections of the aircraft hangars, such as offices
and shops, which communicate with areas for
servicing or storage. Refer to sections 9.3 to
9.5 for proper mounting clearances to com-
bustibles.
C. Heaters must be located so as to be protected
from damage by aircraft and other objects,
such as cranes and movable scaffolding.
D. Heaters must be located so as to be accessible
for servicing and adjustment.
Page 1
/
IL-
ecoSchwank-MILLIVOLT / IL-MILLIVOLT Manual
IM090128
RD: JAN 2009
RL: 1D