Carrier 42C Installation And Start-Up Instructions Manual page 6

Ddc fan coil controller
Table of Contents

Advertisement

FAN (24VAC)
FAN ON (LOW SPEED)
NOT USED
MED SPEED
HIGH SPEED
Baseboard Outputs (J5)
CHANNEL J5 Pins (+,–)
Valve DX1
1, 2*
Valve DX2
3, 2*
HEAT_ST1
5, 4†
HEAT_ST2
5, 6†
*Terminals 1 and 3 provide switched 24 VAC output power to the load.
†J5-5 must be jumpered to 24 VAC + (J1-1).
1
VALVE/DX1 (OPEN)
GROUND
VALVE/DX2 (CLOSE)
Fig. 6 — Fan Coil Controller Baseboard Outputs
Daughter Board Outputs (J6, J7)
CHANNEL TERMINATIONS(+,–)
FAN AC
J6-1, J1-1
FAN ON
J6-2, J1-2
LOW
J6-3, J1-2
MED
J6-4, J1-2
J6-5, J1-2
HI
OAD
J7-1, J7-2
NOTE: J6-1 must be jumpered to 24 VAC +. (J1-1).
2
1
Fig. 5 — Fan Coil Controller Daughter Board Outputs
DESCRIPTION
CONTROL DEVICE
Open
24 VAC, 1A
Close
24 VAC, 1A
Heat Open, 1st Stage
24 VAC, 1A
Heat Close, 2nd Stage
24 VAC, 1A
J5
5
6
2
3
4
DESCRIPTION
CONTROL DEVICE
Fan Input Power
Fan Start/Stop
(Low Speed)
Not Used
Med Speed
High Speed
Outdoor Air Damper
J6
4
5
3
HEAT CLOSE/
STAGE 2
COMMON (24VAC)
HEAT OPEN/
STAGE 1
6
24V, 5A
24V, 5A
24V, 5A
24V, 5A
24V, 5A
24 VAC 1A
J7
1
2
24VAC
OAD
Cool
Warm
Fig. 7 — Space Temperature Sensor
(P/N 33ZCT56SPT Shown)

Advertisement

Table of Contents
loading

This manual is also suitable for:

42d42s42v