Bx5 Service Clearances - Rinnai Brivis StarPro SP623UN Installation Manual

Ducted gas heater
Table of Contents

Advertisement

Diagram 8. External Clearances
Plan View
500 mm min
(Front)
(End)
300 mm
min

3.4.3 BX5 Service Clearances

Front: A minimum of 500mm must be provided at the side facing away from the house.
End: A minimum of 300mm must be provided at each end of the heater.
Top: A minimum of 1000mm must be provided above the heater roof. This clearance must be maintained for the
entire surface area of the heater roof.
Diagram 9. BX5 Clearances
Plan View
500 mm min
(Front)
300 mm
(End)
min
Rinnai
Service Clearance
300 mm
Service Clearance
300 mm
min
1000 mm min
(End)
min
1000 mm min
(End)
15
Service
Clearance
(Top)
Service
Clearance
(Front)
500 mm
min
Service
Clearance
(Top)
Service
Clearance
(Front)
500 mm
min
Ducted Gas Heater IM
Side View
Flashing
Side View
Flashing