4.5.1.1 Wiring topic

4.5 Serial interfaces for communication with PLCs or devices
Shielded cables must be used.
l
The maximal baud rate depends on the cable length
l
Tab. 11: RS-232 cable length based on baud rate
Cable length
2,5 m
5 m
10 m
15 m
30 m
When preparing connections, ensure that the cable shield has a low
impedance connection with the connector housing.
XV360 Single Touch Display 07/19 MN048025EN www.eaton.eu
Max. baud rate
115200 Bit/s
57600 Bit/s
38400 Bit/s
19200 Bit/s
9600 Bit/s