Diagnosis
Abnormality /
display
Protection control
Abnormal wiring or
H41
piping connection
ECONAVI sensor
H59
abnormality
Outdoor high
H64
pressure sensor
abnormality
Light sensor
H70
abnormality
Outdoor fan motor
H97
mechanism lock
Indoor high pressure
H98
protection
Indoor operating unit
H99
freeze protection
4-way valve
F11
switching
abnormality
Indoor standby units
F17
freezing abnormality
Power factor
correction
F90
(PFC) circuit
protection
Refrigeration cycle
F91
abnormality
Compressor
F93
abnormal revolution
Compressor
F94
discharge overshoot
protection
Outdoor cooling high
F95
pressure protection
Power transistor
F96
module overheating
protection
Compressor
F97
overheating
protection
Total running current
F98
protection
Outdoor direct
F99
current (DC) peak
detection
Abnormality
Protection
Judgment
Operation
Continuous for 25s
Continuous for 1
minutes
Continuous for 24
hours, 15days
2 times happen
within 30 minutes
4 times happen
within 30 minutes
3 times happen
within 40 minutes
4 times happen
within 10 minutes
2 times happen
within 20 minutes
4 times happen
within 20 minutes
4 times happen
within 30 minutes
4 times happen
within 20 minutes
4 times happen
within 30 minutes
3 times happen
within 30 minutes
3 times happen
within 20 minutes
Continuous
happen for 7 times
Problem
Wrong wiring and
connecting pipe, expansion
valve abnormality
ECONAVI sensor open or
short circuit
High pressure sensor open
circuit during compressor
stop
Light sensor open or
short circuit
Outdoor fan motor lock or
feedback abnormal
Indoor high pressure
protection (Heating)
Indoor freeze protection
(Cooling)
4-way valve switching
abnormal
Wrong wiring and
connecting pipe, expansion
valve leakage, indoor heat
exchanger sensor open
circuit
Power factor correction
circuit abnormal
Refrigeration cycle
abnormal
Compressor abnormal
revolution
Compressor discharge
pressure overshoot
Cooling high pressure
protection
Power transistor module
overheat
Compressor overheat
Total current protection
Power transistor module
current protection
104
Check location
 Check indoor/outdoor
connection wire and connection
pipe
 Expansion valve and lead wire
and connector
 ECONAVI sensor (defective or
disconnected)
 ECONAVI PCB
 High pressure sensor
 Lead wire and connector
 Light sensor (defective or
disconnected)
 Outdoor fan motor lead wire
and connector
 Fan motor lock or block
 Check indoor heat exchanger
 Air filter dirty
 Air circulation short circuit
 Check indoor heat exchanger
 Air filter dirty
 Air circulation short circuit
 4-way valve
 Lead wire and connector
 Check indoor/outdoor
connection wire and pipe
 Indoor heat exchanger sensor
lead wire and connector
 Expansion valve lead wire and
connector
 Outdoor PCB faulty
 Insufficient refrigerant or valve
close
 Power transistor module faulty
or compressor lock
 Check refrigeration system
 Check refrigeration system
 Outdoor air circuit
 PCB faulty
 Outdoor air circuit (fan motor)
 Insufficient refrigerant
 Check refrigeration system
 Power source or compressor
lock
 Power transistor module faulty
or compressor lock