Checking the usage
JSAV
Safety shut-off valve for securing downstream fittings
against excess gas pressure.
This function is only guaranteed when used within
the specified limits – see page 7 (Technical data).
Any other use is considered as non-compliant.
Type code
Code
JSAV
50 – 100
F
A
40
Inlet pressure p
/1
-0
Part designations
2
3
4
1
Measuring unit
2
Breather screw plug
3
Impulse line connection
4
Inlet
5
Outlet
6
Arrow of direction of flow
7
Reset
8
Arrow of direction of reset
9
Reset lever
Type label
Max. inlet pressure, upper trip pressure p
temperature: see type label.
D-49018 Osnabrück, Germany
JSAV
Description
Safety shut-off valve
Nominal size
Flange to ISO 7005
ANSI flange
= 4 bar (58 psig)
u max.
Trip pressure p
Without pressure test point
1
7
5
8
9
6
, ambient
do
P
max:
u
Wh
:
o
p
:
do
AGo: +/- 10%
TS=
Installation
CAUTION
Please observe the following to ensure that the
JSAV is not damaged during installation:
–
Sealing material, cuttings and other impurities
must not be allowed to get into the housing.
–
We recommend installing a filter upstream of the
JSAV in order to protect it against impurities in
the pipe.
–
The installation location must be dry. Do not
store or install the JSAV in the open air.
–
Install the JSAV in the pipe free of mechanical
stress.
–
Do not clamp the unit in a vice or use it as a
do
lever. Risk of external leakage.
–
Max. inlet pressure p
–
Installation in the vertical or horizontal position,
never upside down.
1 The housing must not be in contact with ma-
sonry. Minimum clearance 20 mm (0.78"). Ensure
that there is sufficient space for installation and
adjustment.
2 Insert seal between pipe and unit.
3 Remove the adhesive foil from the inlet and outlet
on the JSAV.
▷ Note direction of flow.
▷ We recommend installing a manual valve AKT 25
in the pipe leading to the safety relief valve
VSBV 25, so that the annual function check of
the safety shut-off valve JSAV can be carried out
without having to remove it.
GB-2
4 bar (58 psig).
u max.