Checking The Usage; Type Code; Part Designations; Type Label - Krom Schroder JSAV 50 Operating Instructions Manual

Safety shut-off valve
Table of Contents

Advertisement

Checking the usage

JSAV

Safety shut-off valve for securing downstream fittings
against excess gas pressure.
This function is only guaranteed when used within
the specified limits – see page 7 (Technical data).
Any other use is considered as non-compliant.

Type code

Code
JSAV
50 – 100
F
A
40
Inlet pressure p
/1
-0

Part designations

2
3
4
1
Measuring unit
2
Breather screw plug
3
Impulse line connection
4
Inlet
5
Outlet
6
Arrow of direction of flow
7
Reset
8
Arrow of direction of reset
9
Reset lever

Type label

Max. inlet pressure, upper trip pressure p
temperature: see type label.
D-49018 Osnabrück, Germany
JSAV
Description
Safety shut-off valve
Nominal size
Flange to ISO 7005
ANSI flange
= 4 bar (58 psig)
u max.
Trip pressure p
Without pressure test point
1
7
5
8
9
6
, ambient
do
P
max:
u
Wh
:
o
p
:
do
AGo: +/- 10%
TS=

Installation

CAUTION
Please observe the following to ensure that the
JSAV is not damaged during installation:
Sealing material, cuttings and other impurities
must not be allowed to get into the housing.
We recommend installing a filter upstream of the
JSAV in order to protect it against impurities in
the pipe.
The installation location must be dry. Do not
store or install the JSAV in the open air.
Install the JSAV in the pipe free of mechanical
stress.
Do not clamp the unit in a vice or use it as a
do
lever. Risk of external leakage.
Max. inlet pressure p
Installation in the vertical or horizontal position,
never upside down.
1 The housing must not be in contact with ma-
sonry. Minimum clearance 20 mm (0.78"). Ensure
that there is sufficient space for installation and
adjustment.
2 Insert seal between pipe and unit.
3 Remove the adhesive foil from the inlet and outlet
on the JSAV.
▷ Note direction of flow.
▷ We recommend installing a manual valve AKT 25
in the pipe leading to the safety relief valve
VSBV 25, so that the annual function check of
the safety shut-off valve JSAV can be carried out
without having to remove it.
GB-2
4 bar (58 psig).