Krom Schroder JSAV 50 Operating Instructions Manual

Safety shut-off valve

Advertisement

Quick Links

03250885 Edition 10.12
D
GB
F
NL
I
TR
CZ
PL
RUS
H
 
Operating instructions
Safety shut-off valve
JSAV 50 - 100
Translation from the German
© 2012 Elster GmbH

Contents

Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Safety. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Checking the usage . . . . . . . . . . . . . . . . . . . . . 2
Type code . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Part designations . . . . . . . . . . . . . . . . . . . . . . . . 2
Type label. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Connecting the impulse line . . . . . . . . . . . . . . 3
Tightness test . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Checking the function . . . . . . . . . . . . . . . . . . . 4
Replacing the spring . . . . . . . . . . . . . . . . . . . . 4
Resetting. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Replacing the measuring unit. . . . . . . . . . . . . 5
Replacing the valve disc . . . . . . . . . . . . . . . . . 6
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Technical data . . . . . . . . . . . . . . . . . . . . . . . . . 7
Designed lifetime . . . . . . . . . . . . . . . . . . . . . . . . 7
Declaration of conformity . . . . . . . . . . . . . . . . 8
Contact . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
E
DK
S
N
P
GR
www.docuthek.com
. . . . . . . . . . . . . 4
. . . . . . . . . . . . . 4

Safety

Please read and keep in a safe place
Please read through these instructions
carefully before installing or operating. Following the
installation, pass the instructions on to the opera-
tor. This unit must be installed and commissioned
in accordance with the regulations and standards
in force. These instructions can also be found at
www.docuthek.com.
Explanation of symbols
• , 1 , 2 , 3 ... = Action
= Instruction
Liability
We will not be held liable for damage resulting from
non-observance of the instructions and non-com-
pliant use.
Safety instructions
Information that is relevant for safety is indicated in
the instructions as follows:
DANGER
Indicates potentially fatal situations.
WARNING
Indicates possible danger to life and limb.
CAUTION
Indicates possible material damage.
All interventions may only be carried out by qualified
gas technicians. Electrical interventions may only be
carried out by qualified electricians.
Conversion, spare parts
All technical changes are prohibited. Only use OEM
spare parts.
Transport
On receipt of the product, check that the delivery is
complete (see Part designations). Report any trans-
port damage immediately.
Storage
Store the product in a dry place. Ambient tempera-
ture: see Technical data.
Changes to edition 08.12
The following chapters have been changed:
- Declaration of conformity
- JSAV 25 - 40, see operating instructions
for safety shut-off valves JSAV 25 - 40 →
www.docuthek.com → Elster Kromschröder →
Products → 02 Pressure regulators → Safety
shut-off valves JSAV → Kind of document: Op-
erating instructions → JSAV 25 - 40
GB-1

Advertisement

Table of Contents
loading

Summary of Contents for Krom Schroder JSAV 50

  • Page 1: Table Of Contents

    Contents Indicates potentially fatal situations. Safety shut-off valve JSAV 50 – 100 ..1 WARNING Contents ......1 Indicates possible danger to life and limb.
  • Page 2: Checking The Usage

    Checking the usage Installation JSAV CAUTION Safety shut-off valve for securing downstream fittings Please observe the following to ensure that the against excess gas pressure. JSAV is not damaged during installation: This function is only guaranteed when used within – Sealing material, cuttings and other impurities the specified limits –...
  • Page 3: Connecting The Impulse Line

    ▷ To prevent the VSBV from being unintentionally Tightness test shut off, we recommend removing the manual valve lever after commissioning and attaching WARNING it to the pipe. – An additional tightness test must be carried out on the JSAV at all joints which have been JSAV opened for maintenance work or replacement of spare parts.
  • Page 4: Checking The Function

    Checking the function Setting the trip pressure p 1 Select the trip pressure p according to the Checking the trip pressure p outlet pressure p of the pressure regulator. The JSAV is checked for the required trip pressure p 1 Vent the system. ▷...
  • Page 5: Resetting

    8 Screw in the breather screw plug. Replacing the measuring unit 9 After inserting the spring, take the spring’s label ▷ The measuring unit has to be replaced if the from the packaging and stick it below the type JSAV no longer opens or can no longer be reset. label on the JSAV.
  • Page 6: Replacing The Valve Disc

    Replacing the valve disc Press the spring wire ▷ The valve disc has to be replaced if the JSAV is into the notch leaking or has been damaged during resetting. in the plate. ▷ We recommend cleaning the O-ring seats and lightly greasing the O-rings with Klüber Nontrop ZB91 DIN before installation.
  • Page 7: Maintenance

    Designed lifetime Maintenance The Pressure Equipment Directive (PED) and the In order to ensure smooth operation: check the func- Energy Performance of Buildings Directive (EPBD) tion and tightness of the JSAV every year, or every demand regular checks on and maintenance of six months if operated with biologically produced heating systems in order to ensure a high level of methane, see page 4 (Checking the function)
  • Page 8: Declaration Of Conformity

    Declaration of conformity We, the manufacturer, hereby declare that the prod- ucts JSAV 50 – 100, marked with the product ID No. CE-0085AR0246, comply with the requirements of the listed Directives and Standards. Directives: – 90/396/EEC – 97/23/EC Standard: –...