Project design and programming
Parameter: "Restart of staircase time after end of permanent ON"
In the setting "no", the lighting is switched off if the maintained lighting has
ended. In the setting "yes", the lighting remains switched on and the
staircase lighting is restarted.
Parameter: "Warning during dimming down (object 'Warning stairc.
lighting')"
The user can be also be warned during the dimming down period, whereby
the object "Warning stairc. lighting" is set to "1".
Parameter: "Duration of staircase lighting can be changed by object"
The object "Duration of staircase lighting" is enabled via this parameter. It
enables the modification of the staircase lighting time via the bus.
Parameter: "After staircase lighting the staircase light is"
It can be set here whether the staircase lighting is switched on or off after
recovery of the supply voltage (mains voltage).
switched on
The lighting is switched on and the staircase lighting time is
started.
switched off
The lighting is switched off.
The output also follows this parameter on recovery of the bus voltage and
after supply voltage recovery.