Initial Power On

Apply power to the base power supply. The P
indicating that power is being supplied to the base connectors. The controller will take a few seconds to
complete the startup sequence.

Module Status Indicators

When this is complete, the status indicators should be in the state as shown in the table below:
Indicator
State
CPU G
ON
OOD
RUN
OFF*
B
G
ON
ATTERY
OOD
The Multi-Segment Display (MSD) should display the four octets of the IP address, three characters at a
time. For example, if the IP address is set to 192.10.100.1, the MSD will display 192 then 010, then 100, and
then 001. If no IP address has been set, the MSD will display an IP address of 000.000.000.000. Firmware
version 8.02 and above will also display the network mask in CIDR format. The CIDR number will be
preceded by an underline character "_". See the CTI 2500 Series Controller Installation and Operation Guide
for additional information regarding CIDR format.
If the MSD displays "U01", the controller is in Firmware Update mode. Remove power, set SW12 to the
If the MSD displays "Enn" (where n represents a number), an error has occurred during startup. See the

Setting the Controller IP Parameters

Using the Serial or USB Port
When connected to the serial or USB port, you can set the IP address and other IP parameters using PLC
Workshop (V4.11 or greater) or IPSET, a standalone utility that you can download from the CTI web site.
Using the Ethernet Port
Firmware version 8.02 and above allows you to set the IP address and other IP parameters when connected
to the Ethernet port. To enable this capability, SW11 must be set to the closed position. You can change the
parameters using PLC Workshop (V4.11 or greater) or by accessing the 2500 controller embedded web
server with your PC web browser.
Page 4
OWER
Comments
If the CPU G
LED is off, check the Multi-
OOD
Segment Display (MSD). If the MSD is
displaying FE, a fatal error is present and
must be cleared. See the CTI 2500 IOG for
additional information.
* If this is the first time you have powered the
controller since installing the battery, the
controller will be in Program mode and the
LED will be OFF. Otherwise, the controller
will be in either PROGRAM or RUN mode,
depending on the state at power down.
If a good battery has been installed and the
Battery Switch has been set to ON, this LED
will illuminate. If the LED is off, the battery is
missing or bad or the battery switch is off.
closed position, and re-apply power to the controller.
Installation and Operation Guide for steps to clear the error.
G
LED on the power supply should illuminate,
OOD
NOTE:
CTI 2500 Series Compact Controller Quick Start Guide