Maximum cable lengths:
300 m (984 ft) between activation switch [K] and drive control unit
60 m (200 ft) between multiple drives
60 m (200 ft) between external power supply and first drive.
Note: The voltage at the INx terminals of the control unit must be at least 17 V DC to be
interpreted as "1".

Grounding of protective shields

Ground the shield in the cabling between the activation switch and the control unit at
the control unit.
Ground the shield in the cabling between two control units at one control unit only.

Single drive (internal power supply)

Dual-channel connection

ACS880-04F
Control unit
Control logic
OUT1
+24 V
SGND
IN1
IN2
UDC+
A
UDC–
Safe torque off function 155
T1/U2, T2/V2, T3/W2
K