Siemens SENTRON 5TT7 System Manual page 30

Gsm alarm module
Table of Contents

Advertisement

Module
2.5 Configuring
SMS instruction/user-defined commands
It is possible to switch the outputs individually or in a group with the user-defined or default
commands.
With these commands, you can activate an output (SMS instruction for activation),
deactivate it (SMS instruction for deactivation) or activate it for a specific period of time (SMS
instruction for one-shot activation).
In this way, you can switch all outputs with user-defined commands, for instance, "pumpon
for switching on and "pumpoff
With this function, it is also possible to switch several module outputs with one command at
the same time by defining the same command for these outputs.
It is also possible to combine commands, to simultaneously activate an output, deactivate
another one and activate a third one only for a specific period of time.
Number ID
You deactivate checking of the caller's telephone number by unchecking the 'Number ID'
box.
When this setting is made, the output responds to telephone calls or SMS messages from
any sources.
Note
Please consider the possible risks when using this function together with the ring function.
Switching a single digital output
To set one single digital output (DO), send the "wdonx
the number of the output and "'x" is its status.
The x stands for the respective output's status: 0 = Off, 1 = On, 2 = no change and 3 =
change over.
For example, if you send the "wdo31
If a specific name is assigned to an output (in "Digital output name:"), you can switch this
output by putting the name between asterisks in the SMS text sent.
For example, you can change over an output named 'Light' by sending the "w*light*3" SMS.
If sending of a confirmation message is set, the module sends an SMS message in the form
of "status DOn=x" or if you have defined a name: „status name=x".
The "Status not changed" text is added in the module's reply if an output is already in the
desired status and does not need to be switched.
30
"
for switching off.
" SMS
to the module, the digital output DO3 is set to 1.
" SMS text
to the module, where "'n" is
System Manual, 06/2014, 2541304131-01
"
GSM alarm module

Advertisement

Table of Contents
loading

Table of Contents