7.2 Advanced Digital Control
Display and Keypad
The Advanced Digital Control has an LED display and a
three-button keypad. See Figure 7-2. The LED display
shows runtime hours, fault codes, application program
version number, or controller parameters during
configuration and adjustment. See Figure 7-3. The
keypad is used to enter the controller's configuration
and adjustment menus, and to change the controller
settings.
A password key sequence is required to enter the
configuration and adjustment menus.
contains the instructions to enter the configuration and
adjustment menus and change the settings using the
controller keypad.
1
2
1. LED display
2. Select button (use for setup and adjustment only)
3. Up and down arrow buttons (use for setup and adjustment only)
4. Generator set master switch
Figure 7-2 Advanced Digital Control
46
Section 7 Controller
Section 7.5
3
GM28707A-C
4
Controller Display
Item
Description
Crank indication
Displays CC_1, CC_2, or CC_3 to indicate
the 1st, 2nd or 3rd attempt to start the
engine. The last digit flashes during the
crank cycle rest periods.
Runtime hours
Displays total generator set runtime hours
when no other code is displayed.
Fault codes
Flashes a 2- or 3-letter fault code to indicate
various fault conditions. See Section 7.4.
System
Displays 2-letter codes or 4-digit
parameters
alphanumeric codes during system
configuration or adjustment. See Section 7.5.
Application
Displays the version number of the
program version
controller's application program before
number
entering the configuration or adjustment
mode. See Section 7.6.
Figure 7-3 Advanced Digital Control's LED Display