Section 10: Metal-clad switchgear field
taping procedure (38 kV)
10.1 Busbar taping
Materials for taping
Reference Figures 33 and 34 below for details on proper busbar
taping .
Filler: A putty-like material:
Trade name: Scotchfil
or Nashau 102
®
may be used .
Insulating tape and pad – High voltage EPR insulating tape:
Trade name: Scotch 130C .
10.2 Using an insulating boot
Step 1: Clean the area of dirt and foreign matter . Use a clean, dry
cloth or, if necessary, dampen slightly with distilled water .
Do not use any abrasives or solvents .
Step 2: Place the boot over the joint so it fits in place . Fasten
together with plastic wire ties . Cut off excess ends of plas-
tic wire ties .
10.3 Cable termination taping
If cable termination insulation boots are not provided, Eaton recom-
mends using tape material, Trade name: Scotch 130C, for all cable
termination insulation . Refer to 3M's taping method instructions,
Tape Method for Insulating Bus-Bar Connections 5-35 kV to meet
ANSI C37 .20 Requirements, for installation techniques when using
this tape .