Connect; Personnel Requisition; Requirements; Connection Options - Wilo Yonos MAXO Installation And Operating Instructions Manual

Table of Contents

Advertisement

6

Connect

6.1

Personnel requisition

The electrical connection may only be performed by a
qualified electrician.
6.2

Requirements

ATTENTION
Wrong connection of the pump leads to damage to the
electronics.
Observe voltage rating on the rating plate.
Maximum back-up fuse: 10 A, inactive or circuit breaker
with C characteristic
Never connect to an uninterruptible power supply or
IT-networks.
During external connection of the pump deactivate a
pulse of the voltage (for example phase angle control).
Switching the pump via triacs/solid-state relays must be
examined on a case-by-case basis.
During deactivation with on-site power relay:
Rated current ≥ 10 A, rated voltage 250 V AC
Note switching frequency:
– Switching on/off mains voltage ≤ 100/24 h
– ≤ 20/h at a switching frequency of 1 min between
switching on/off via mains voltage
Secure pump with a residual-current device (type A or B).
Leakage current I
≤ 3.5 mA
eff
The electrical connection must be made via a fixed
connecting cable equipped with a connector device or an
all-pole switch with a contact opening width of at least
3 mm (VDE 0700/Part 1).
To protect against leakage and for strain relief to the
threaded cable connection use a connection pipe with
sufficient outer diameter.
Use a heat-resistant connecting cable where fluid tem-
peratures exceed 90 °C.
Lay the connection pipe in such a way that it touches
neither the pipes nor the pump.
6.3

Connection options

Fig. 14: Connection options
The pump can be connected to networks with the fol-
lowing voltage ratings:
1~ 230 V
3~ 400 V with neutral conductor
3~ 400 V without neutral conductor (upstream power
transformer)
3~ 230 V
6.4

Double pumps

Only operate as main and standby pump with automatic
fault-actuated switchover:
Individually connect and secure both motors.
Provide separate switchgear.
Make the identical settings.
6.5

Collective fault signal (SSM)

The contact of the collective fault signal (potential-free
normally closed contact) can be connected to a build-
ing automation system. Internal contact is closed in the
following cases:
The pump has zero current.
There is no fault.
The control module has failed.
DANGER
Danger to life through voltage transmission, if mains and
SSM pipe are led together through a 5-wire cable.
Do not connect SSM pipe to protective low voltage.
Use 5 x 1.5 mm² cable.
Connection
minimum 12 V DC, 10 mA
maximum 250 V AC, 1 A
During connection of the SSM pipe to the network po-
tential:
SSM phase = live wire L1
6.6
Connect
DANGER
During connection of the pump risk of death from electric
shock!
Disconnect power supply before starting work.
Only allow qualified electricians to carry out electrical
connection.
Fig. 15: Preparing the connection
1.
Disconnect power supply.
Connect
EN
9