Carrier 48GC04 Service And Maintenance Instructions page 8

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

RPM
Field Accessories:
NOTE: Values in the Field Accessories section are RPM adders.
Fig. 11 — Example of Fan Speed Set Up Labels for SystemVu™ Controls
TROUBLESHOOTING THE ECM MOTOR
EcoBlue™ motors are designed with several built-in protections
included in the motor software. If the motor detects a fault it will
safely shut down. For temperature related faults the motor re-
quires a line voltage reset to continue operation. For all others,
the motor will resume operation automatically as soon as the
fault condition is cleared. See Table 3 for a complete list.
Table 3 — Fault Condition/Reset Trigger
Fault
Reset
Condition
Trigger
Phase Failure
Automatic
Locked/ Blocked
Automatic
Rotor
Motor Over
Manual
Heated
Power Module
Manual
Over Heated
Line under-
Automatic
voltage
Communication
Automatic
Error
Calculator
0.2
0.4
1425
1609
1500
1512
1688
1625
1601
1768
1750
1692
1850
1875
1784
1933
2000
1878
2018
2125
1973
2104
2250
2069
2192
2375
2166
2282
2500
65
65
Economizer
Description
One phase is missing or imbalanced. In
this case the motor will come to a stop
and then automatically restart when all
phases are present.
The rotor is blocked. Once the locking
mechanism has been removed, the
motor will automatically restart.
The motor will stop in the event the
motor over heats. In this case there has
to be a manual restart.
The motor will stop in the event the
electronics over heat. In this case there
has to be a manual restart.
Once the line voltage returns within
permitted operating range, the fan will
automatically restart.
Internal communication error of the
fan's electronics. The fan will restart
automatically, if error is cleared.
ESP in. wg
0.6
0.8
1.0
1.2
1764
1902
2028
2147
1839
1974
2097
2212
1916
2047
2168
2280
1994
2123
2241
2351
2073
2200
2316
2153
2277
2235
2356
2317
65
65
65
65
Troubleshooting the motor requires a voltmeter.
1.
Disconnect main power to the unit.
2.
Disconnect motor plug in supply section of the unit.
3.
Restore main unit power.
4.
Check for proper line voltage at motor power leads Black
(PL1-1), Yellow (PL1-2), and Blue (PL1-3). Blue is only
present on 3-phase motors. See the following table.
48GC Unit Voltage
208/230
460
575
5.
Disconnect main power.
6.
Reconnect motor plug in supply section of unit.
7.
Restore main power.
8.
Check for proper motor control voltage signal of 9.7Vdc to
10.3Vdc at IFM-1 and IFM-3 on Unit Control Board (UCB).
See Fig.12 for 3 phase units and see Fig. 13 for 1 phase units.
9.
Using a jumper wire from unit control terminals R to G,
engage motor operation.
10. Verify control signal from user speed selection switch by
placing voltmeter taps in provided terminals marked Vdc.
Signal should be between 3.8Vdc and 10.3Vdc.
11. If the motor does not start and run, remove the fan assem-
bly and replace the motor with one having the same part
number. Do not substitute with an alternate design motor
as the voltage/speed programming will not be the same as
that on an original factory motor.
8
1.4
1.6
1.8
2.0
2260
2367
2322
2387
65
65
Motor Voltage
230
460
575
Min-Max Volts
187-253
360-506
517-633

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48gc06

Table of Contents