Indicators; Troubleshooting - Carrier 48GC04 Service And Maintenance Instructions

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

SAMPLING
TUBE
AIRFLOW
Fig. 44 — Sensor Cleaning Diagram
3.
Squeeze the retainer clips on both sides of the optic housing.
4.
Lift the housing away from the printed circuit board.
5.
Gently remove dirt and debris from around the optic plate
and inside the optic housing.
6.
Replace the optic housing and sensor cover.
7.
Connect power to the duct detector then perform a sensor
alarm test.

Indicators

NORMAL STATE
The smoke detector operates in the normal state in the absence
of any trouble conditions and when its sensing chamber is free
of smoke. In the normal state, the Power LED on both the sen-
sor and the controller are on and all other LEDs are off.
ALARM STATE
The smoke detector enters the alarm state when the amount of
smoke particulate in the sensor's sensing chamber exceeds the
alarm threshold value. (See Table 6.) Upon entering the alarm
state:
The sensor's Alarm LED and the controller's Alarm LED
turn on.
The contacts on the controller's two auxiliary relays switch
positions.
The contacts on the controller's alarm initiation relay
close.
The controller's remote alarm LED output is activated
(turned on).
The controller's high impedance multiple fan shutdown
control line is pulled to ground Trouble state.
The SuperDuct™ duct smoke detector enters the trouble state
under the following conditions:
A sensor's cover is removed and 20 minutes pass before it
is properly secured.
A sensor's environmental compensation limit is reached
(100% dirty).
A wiring fault between a sensor and the controller is detected.
An internal sensor fault is detected upon entering the trouble
state:
The contacts on the controller's supervisory relay switch
positions. (See Fig. 45.)
If a sensor trouble, the sensor's Trouble LED the control-
ler's Trouble LED turn on.
If 100% dirty, the sensor's Dirty LED turns on and the
controller's Trouble LED flashes continuously.
If a wiring fault between a sensor and the controller, the
controller's Trouble LED turns on but not the sensor's.
CONTROL OR
HVAC DUCT
INDICATOR
SENSOR
Magnetic test/
HOUSING
reset switch
Alarm LED
Trouble LED
OPTIC
PLATE
Dirty LED
Power LED
RETAINER
CLIP
OPTIC
HOUSING
ALARM
NOTE: All troubles are latched by the duct smoke detector. The
trouble condition must be cleared and then the duct smoke detec-
tor must be reset in order to restore it to the normal state.
RESETTING ALARM AND TROUBLE CONDITION TRIPS
Manual reset is required to restore smoke detector systems to
Normal operation. For installations using two sensors, the duct
smoke detector does not differentiate which sensor signals an
alarm or trouble condition. Check each sensor for Alarm or
Trouble status (indicated by LED). Clear the condition that has
generated the trip at this sensor. Then reset the sensor by press-
ing and holding the reset button (on the side) for 2 seconds.
Verify that the sensor's Alarm and Trouble LEDs are now off.
At the controller, clear its Alarm or Trouble state by pressing
and holding the manual reset button (on the front cover) for 2
seconds. Verify that the controller's Alarm and Trouble LEDs
are now off. Replace all panels.

Troubleshooting

CONTROLLER'S TROUBLE LED IS ON
1.
Check the Trouble LED on each sensor connected to the
controller. If a sensor's Trouble LED is on, determine the
cause and make the necessary repairs.
2.
Check the wiring between the sensor and the controller. If
wiring is loose or missing, repair or replace as required.
CONTROLLER'S TROUBLE LED IS FLASHING
1.
One or both of the sensors is 100% dirty.
2.
Determine which Dirty LED is flashing then clean that sen-
sor assembly as described in the detector cleaning section.
SENSOR'S TROUBLE LED IS ON
1.
Check the sensor's Dirty LED. If it is flashing, the sensor
is dirty and must be cleaned.
2.
Check the sensor's cover. If it is loose or missing, secure
the cover to the sensor housing.
3.
Replace sensor assembly.
SENSOR'S POWER LED IS OFF
1.
Check the controller's Power LED. If it is off, determine
why the controller does not have power and make the nec-
essary repairs.
26
Table 6 — Detector Indicators
DESCRIPTION
Resets the sensor when it is in the alarm or trouble
state. Activates or tests the sensor when it is in the
normal state.
Indicates the sensor is in the alarm state.
Indicates the sensor is in the trouble state.
Indicates the amount of environmental
compensation used by the sensor (flashing
continuously = 100%)
Indicates the sensor is energized.
POWER
TROUBLE
ALARM
RESET
Fig. 45 — Controller Assembly
TROUBLE
POWER
TEST/RESET
SWITCH

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

48gc06

Table of Contents