Carrier 48GC04 Service And Maintenance Instructions page 58

Single package rooftop gas heat/electric cooling unit with puron (r-410a) refrigerant 3 to 5 nominal tons
Table of Contents

Advertisement

2SP H/C (2 Speed Heat/Cool) Fan Operation
FAN TYPE = 2SP H/C is not used on 48GC units.
3 Speed Fan Operation (single phase units only)
The W7220 controller does not actually control the fan speed
or the heat output of the unit, and only uses this information to
help determine the damper position. On single phase units, the
unit control board (UCB) will reduce the fan speed during
heating when the configured fan speed is set outside the opti-
mized heating speed window. If the job site application forces
DEMAND
OUTSIDE AIR
CONTROLLED
GOOD TO
VENTILATION
ECONOMIZE
(DCV)
NO
NONE
YES
NO
Below CO
Set
2
YES
NO
Above CO
Set
2
YES
*With stage 3 delay (STG3 DLY) in Advanced setup, COOL Y2-OUT will be turned ON after the delay time specified.
N/A = Not applicable
Table 24 — Economizer Operation - FAN TYPE = 3SPEED
INPUTS
W
COOL
(HEAT ON)
Y1-IN
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
ON
N/A
OFF
OFF
OFF
ON
OFF
ON
this reduction in fan speed during heat, the economizer FAN
TYPE must be set to keep the appropriate outside air intake.
On single phase 48GC 3 to 5 ton units, if reduced the heating
fan speed is lower than the high cooling speed and higher than
the low cooling speed, hence the medium speed name. The
economizer FAN TYPE needs to be set to 3SPEED (3 speed).
This indicates that the heating fan speed is between the Low
cool/vent fan speed and the High cool speed. Refer to Table 24
for economizer operation.
FAN SPEED
COOL
COOL
COOL
Y2-IN
Y1-OUT
Y2-OUT
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF*
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF*
N/A
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
ON
ON
ON
N/A
OFF
OFF
OFF
OFF
OFF
OFF
OFF
OFF*
ON
ON
OFF*
58
OUTPUTS
DAMPER POSITION
(reference
OCCUPIED
only)
MEDIUM
MIN POS M
LOW
MIN POS L
LOW
MIN POS L
HIGH
MIN POS H
MEDIUM
MIN POS M
LOW
MIN POS L
MIN POS L to
LOW
Full Open
MIN POS H to
HIGH
Full Open
MEDIUM
VENTMIN M
LOW
VENTMIN L
LOW
VENTMIN L
HIGH
VENTMIN H
MEDIUM
VENTMIN M
LOW
VENTMIN L
VENTMIN L to
LOW
Full Open
VENTMIN H to
HIGH
Full Open
VENTMIN M to
MEDIUM
VENTMAX M
VENTMIN L to
LOW
VENTMAX L
VENTMIN L to
LOW
VENTMAX L
VENTMIN H to
HIGH
VENTMAX H
VENTMIN M to
MEDIUM
VENTMAX M
VENTMIN L to
LOW
VENTMAX L
VENTMIN L to
LOW
Full Open
VENTMIN H to
HIGH
Full Open
UNOCCUPIED
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open
Closed
Closed
Closed
Closed
Closed
Closed
Closed to
Full Open
Closed to
Full Open