5. AF 600 FP Drive Function Code Changes

The AF 600 FP Adjustable Frequency Drive has programmable function. A complete description of these
function codes can be found in DET – 609 or DET – 610. The purpose of this section is to identify those function
codes which changed from the factory defaults for bypass panel installation.
Live Zero Time Out Time
Live Zero Time Out Function (AN01)
Terminal 53 Live Zero
Terminal 54 Live Zero
Jog Speed
Frequency Command 2
Terminal 27 Digital Input
Terminal 32 Digital Input
Terminal 33 Digital Input
Relay 1
Relay 2
Electronic Overload
Motor Thermistor Input
Auto-Reset (Times)
Loss of reference control – Run at preset speed
Main Menu
Parameter data set
Down arrow
AN - ##
OK
DEH40602 – Page 16
(AN00)
Set to "10" seconds
Set to "3" Jogging
(AN17)
Set to "0" Disabled
(AN27)
Set to "1" Enabled
(C20)
Set to "50" Hz
(C30)
Set to "2" Analog Input 54
(E03)
Set to "2" Coast inverse
(E05)
Set to "14" Jog
(E06)
Set to "6" Stop Inverse
(E24)
Set to "9" Alarm
(E24)
Set to "5" Running
(F10)
Set to "4" Elec OL Trip 1
(F12)
Set to "0" None
(H04)
Set to "13" Infinite Auto Reset
Drive Programming
23
AN 11-2021 Rev 05, 12/15/2011