GE AF-600 FP User Manual page 52

Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Device
Load Reactor (6KFP
Series)
Load Reactor (6KFP*L
Series) - 3% Z
Load Reactor (6KFP*L
Series) - 1% Z
Control Terminal Board
Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.
DEH40603 – Page 6
AF - 600 HP Rating(s)
1 through 5
7.5 through 20
25 through 40
50 through 100
125
150
1 through 10
15 through 20
25
30 through 75
100 through 650
1 through 10
15 through 20
25
30
40 through 75
100 through 650
2 through 300
Table – 3 (575V)
Minimum Wire Size
# 22 AWG
# 14 AWG
# 18 AWG
# 6 AWG
# 2 AWG
Note 2
# 22 AWG
# 14 AWG
# 18 AWG
# 6 AWG
Note 2
# 22 AWG
# 14 AWG
# 22 AWG
# 14 AWG
# 6 AWG
Note 2
# 26 AWG
52
Maximum Wire Size
Required Torque
# 10 AWG
# 6 AWG
# 4 AWG
45 (6 - 4AWG), 50
1/0
4/0
Note 2
# 10 AWG
# 6 AWG
# 4 AWG
45 (6 - 4AWG), 50
# 1/0
Note 2
# 10 AWG
# 6 AWG
# 14 AWG
# 6 AWG
45 (6 - 4AWG), 50
# 1/0
Note 2
# 10 AWG
AN 12-1007 Rev 05, 04/04/2012
4.5 lb. in.
16 lb. in.
16 lb. in.
(2-1/0 AWG)
150 lb. in.
Note 1
4.5 lb. in.
16 lb. in.
16 lb. in.
(2-1/0 AWG)
Note 1
4.5 lb. in.
16 lb. in.
16 lb. in.
16 lb. in.
(2-1/0 AWG)
Note 1
Note 1

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents