Measured Values and Parameters SUNNY BOY 2000HF-US/2500HF-US/3000HF-US Technical Description HF_STP_Par-eng-TUS114810 | Version 1.0...
Page 3
All such warranties are expressly disclaimed. Neither SMA America, LLC nor its distributors or dealers nor SMA Solar Technology Canada Inc. nor its distributors or dealers shall be liable for any indirect, incidental, or consequential damages under any circumstances.
Page 4
SMA equipment and/or other equipment connected to the SMA equipment or personal injury. DANGER indicates a hazardous situation which, if not avoided, will result in death or serious injury.
Page 5
SMA America, LLC Important Safety Instructions Other Symbols in this document In addition to the safety and hazard symbols described on the previous pages, the following symbol is also used in this manual: Information This symbol accompanies notes that call attention to supplementary information that you must know and use to ensure optimal operation of the system.
Page 6
All installations must conform with the laws, regulations, codes and standards applicable in the jurisdiction of installation. SMA assumes no responsibility for the compliance or noncompliance with such laws or codes in connection with the installation of the product.
Additional information on specific topics can be found in the download area at www.SMA‑America.com. 1.4 Nomenclature In this document, SMA America Production, LLC and SMA Solar Technology Canada Inc. will be referred to as SMA. 1.5 Communication Protocols Communication protocol DATA I and DATA II+ Depending on the mode of communication (RS485 or Bluetooth®...
1 Notes on this Manual SMA America, LLC 1.6 Measured Values The inverter measures signals during operation. The signals are depicted and stored in a communication device or communication software in the form of measured values. The measured values in this manual are categorized according to communication protocol. For an explanation of the values for Data I, refer to the descriptions under Data II+.
SMA America, LLC 2 DATA I DATA I 2.1 Measured Values Name Description A.Ms.Amp See "DC current input", page 18 A.Ms.Vol See "DC voltage input", page 18 A.Ms.Watt See "DC power input", page 18 ComRev See "Communication version", page 20 Error Event message For more details see chapter 1.8 "Event Messages", page 10.
2 DATA I SMA America, LLC 2.2 Operating Parameters Name Description A.Const.VSet See "Voltage setpoint", page 26 A.StrTms See "Start delay", page 26 A.VStr See "Critical voltage to start feed-in", page 26 AID.AngFact See "Escalation factor", page 36 AMaxOfs See "Tripping threshold DC current monitoring", page 29 AMaxOfsTms See "Tripping time DC current monitoring", page 29 BT.RevVer...
Page 13
SMA America, LLC 2 DATA I Name Description KP.hwRev See "Hardware version of the communication assembly", page 41 KP.swRev See "Firmware version of the communication assembly", page 41 LCD.swRev See "Firmware version of the display", page 41 MainModel See "Device class", page 20 Md.GndAmpMax See "Maximum module ground current", page 31 Md.GndAmpMaxTmms...
Page 14
2 DATA I SMA America, LLC Name Description VolCtl.llLim See "Voltage monitoring of median minimum threshold", page 38 VolCtl.llLimTms See "Voltage monitoring median min. threshold trip.time", page 39 VolCtl.Max See "Voltage monitoring upper maximum threshold", page 37 VolCtl.MaxTmms See "Voltage monitoring upper max. threshold trip. time", page 38 VolCtl.ReconMax...
SMA America, LLC 2 DATA I 2.3 Event Messages Name Description ComFlt See "Communication disturbed", page 49 DcAmpMax See "DC overcurrent", page 47 DcMinFlt See "Start conditions not met", page 48 DcVMax See "DC overvoltage", page 47 DevFlt See "Interference of device", page 48 DscGndModRv See "Grounding error", page 48 FanFlt See "Fan fault", page 50 GndFuFlt See "Grounding error", page 48...
Page 16
2 DATA I SMA America, LLC Name Description UpdBTErr See "Update Bluetooth failed", page 50 UpdEnd Update complete UpdHP Main CPU update active UpdHPErr See "Update main CPU failed", page 50 UpdKom Communication update active UpdLang Language table update active UpdLangErr See "Update language table failed", page 50...
SMA America, LLC 3 DATA II+ DATA II+ 3.1 Measured Values 3.1.1 Status - Operation Name Description Value Explanation Number of events for Counter for events relevant for the plant operator user Number of events for Counter for events relevant for the installer...
3.1.5 DC Side - Insulation monitoring Name Description Insulation resistance Insulation resistance of the PV plant prior to the grid connection in kΩ For inverter with SMA Plug-in Grounding the value should be 0. 3.1.6 AC Side - Operation Name Description Number of grid connections Number of grid connections 3.1.7 AC Side - Measured values...
SMA America, LLC 3 DATA II+ 3.1.8 AC Side - Grid measurements Name Description Reactive power Total reactive power in % Power Delivered active power in W (total) Grid frequency Grid frequency in Hz 3.1.9 AC Side - Grid measurements - Power per phase...
3 DATA II+ SMA America, LLC 3.2 Operating Parameters 3.2.1 Type Label Device class Display of inverter device class Inverter Unit Value range Default setting ― • Solar Inverters Solar inverters Device name Entry of a selected name in the inverter description...
SMA America, LLC 3 DATA II+ Serial number Inverter serial number display Inverter Unit Value range Default setting ― fixed ― 3.2.2 Device - Operation Reset operating data Reset operating counter to default setting. Inverter Value range Default setting • DoAll / Execute all ―...
3 DATA II+ SMA America, LLC Load parameter Return all operating parameters to default setting, except for SMA Grid Guard parameters, which are protected by the Grid Guard Code. Inverter Value range Default setting • DfltParaLod / Load preset ―...
SMA America, LLC 3 DATA II+ 3.2.5 Device - Inverter Deactivation delay This parameter defines the amount of time the inverter will wait before disconnecting from the grid when the feed-in conditions are no longer met. Inverter Unit Value range Default setting 1 …...
3 DATA II+ SMA America, LLC 3.2.6 Device - Multifunction relay Operating mode of multifunction relay You configure the desired operating mode and further settings via parameters. Inverter Unit Value range Default setting ― • FltInd / Fault indication FltInd / Fault indication •...
SMA America, LLC 3 DATA II+ 3.2.9 Device - Multifunction Relay - Battery bank Minimum On power for MFR battery bank Threshold for switching the relay in operating mode 'Charging the battery' Inverter Unit Value range Default setting 100 … 17 000 1 500...
3 DATA II+ SMA America, LLC 3.2.11 DC Side - DC settings Critical voltage to start feed-in Initial voltage required before the inverter begins feeding in power into the grid. If the value is set too low, this may lead to an increased number of connections to the grid, and thus to increased wear.
SMA America, LLC 3 DATA II+ Set feed-in time Setting the feed-in time ("feed in time" measured value) of the inverter Changing this may be necessary if you replace the inverter and want to use feed time from the old device.
3 DATA II+ SMA America, LLC 3.2.14 AC Side - Island mode Endpoint of the power control via frequency Setting the frequency-dependent power reduction This parameter can be used to set the endpoint of the frequency performance curve. Inverter Unit Value range Default setting 0 …...
SB 3000HFUS-30 5 0.063 0.063 0.063 Tripping time DC current monitoring This parameter sets the standard deactivation time for DC current monitoring These parameters may only be changed after prior agreement with the SMA Serviceline. Inverter Unit Value range Default setting ...
Page 30
3 DATA II+ SMA America, LLC Minimum insulation resistance This parameter sets the lower tripping threshold for insulation resistance. This parameter has no effect with the SMA Plug-in Grounding. Inverter Unit Value range Default setting k Ω 500 … 3 000 1 000...
SMA America, LLC 3 DATA II+ Reconnection time upon restart The parameter defines the time to reconnection to the grid after a restart. Inverter Unit Value range Default setting 0 … 400 3.2.17 Grid monitoring - Country standard - PV module Maximum module ground current The inverter disconnects from the grid when this threshold is exceeded.
Page 32
GndModNg / GndModNg / Learning Negative Negative Negative Measures in the case of a grounding error This parameter has no effect with the SMA Plug-in Grounding. Inverter Unit Value range Default setting ― • GndFltDscon / Disconnect from grid GndFltWrn / Warn •...
SMA America, LLC 3 DATA II+ 3.2.18 Grid monitoring - Frequency monitoring The following parameters define the triggering times and corresponding triggering thresholds of the inverter frequency monitoring. The "set country standard" parameter can be used to restore the desired standard.
Page 34
3 DATA II+ SMA America, LLC Frequency monitoring upper minimum threshold The inverter switches off below this threshold. Inverter Unit Value range Default setting 44 … 60 see below Inverter Setting OFF-Grid60 UL1741/2005 UL1741/2005/ UL1741/2005/ 59.3 59.3 59.3 Frequency monitoring lower minimum threshold The inverter switches off below this threshold.
Page 35
SMA America, LLC 3 DATA II+ Frq. monitoring upper min. threshold trip. time The inverter switches off after the tripping time below this threshold. Inverter Unit Value range Default setting 0 … 300 000 see below Inverter Setting OFF-Grid60 UL1741/2005...
Escalation factor Parameter for activation of the island grid identification. These parameters may only be changed after prior agreement with the SMA Serviceline. This parameter can be used to set the starting point of the frequency output characteristic curve. Inverter...
Page 37
SMA America, LLC 3 DATA II+ Voltage monitoring upper maximum threshold The inverter switches off when this threshold is exceeded. Inverter Unit Value range Default setting 300 … 420 see below Inverter Setting OFF-Grid60 UL1741/2005 UL1741/2005/ UL1741/2005/ Voltage monitoring median maximum threshold The inverter switches off when this threshold is exceeded.
Page 38
3 DATA II+ SMA America, LLC Voltage monitoring upper minimum threshold The inverter switches off below this threshold. Inverter Unit Value range Default setting 60 … 240 see below Inverter Setting OFF-Grid60 UL1741/2005 UL1741/2005/ UL1741/2005/ 105.6 183.1 211.2 Voltage monitoring of median minimum threshold The inverter switches off below this threshold.
Page 39
SMA America, LLC 3 DATA II+ Voltage monitoring lower max. threshold trip. time The inverter switches off after the tripping time after this threshold is exceeded. Inverter Unit Value range Default setting 0 … 10 000 see below Inverter Setting...
OFF-Grid60 UL1741/2005 UL1741/2005/ UL1741/2005/ 3.2.21 Plant communication Maximum Bluetooth transmission power Parameter for setting the Bluetooth transmission performance These parameters may only be changed after prior agreement with the SMA Serviceline. Inverter Unit Value range Default setting 1 … 20 HF_STP_Par-eng-TUS114810...
SMA America, LLC 3 DATA II+ 3.2.22 Device Components Name Description Firmware version of the Software version of the component present in the inverter Bluetooth component Serial number of the Bluetooth Serial number of the component present in the inverter component...
Page 42
3 DATA II+ SMA America, LLC Name Description Firmware version of the central Software version of the component present in the inverter assembly Hardware version of the central Version number of the component present in the inverter assembly Serial number of the central...
If the grid voltage lies within the tolerance range, yet this error is still being displayed, contact the SMA Serviceline. Grid overvoltage Spot value for the grid voltage measurement with...
Page 44
If the grid voltage lies within the tolerance range, yet this error is still being displayed, contact the SMA Serviceline. Grid undervoltage fast The effective value of the grid voltage has fallen below the lower minimum grid voltage level for the set triggering time.
Page 45
If the grid voltage is continually within the acceptable range, and this error is still displayed, contact the SMA Serviceline. Voltage increase protection The effective value of the grid voltage is above the permitted threshold for a specified period of time (country parameters, e.g., 10 minutes).
Page 46
Discuss the proposed parameters with the SMA Serviceline. Grid frequency disturbance The average grid frequency is outside the specified limit for a defined period of time.
Page 47
3502 Ground fault detected Ground fault detected 3503 Overcurrent Ground fuse Too much current at the SMA Plug-in Grounding DC overcurrent An overcurrent condition occurs on the DC side of the inverter and it switches off. Corrective measures: • If this event recurs frequently, check the PV generator design and connection.
Page 48
• If this event recurs at medium irradiation, check the PV plant design and correct the connection of the PV generator. Grounding error The polarity of the SMA Plug-in Grounding does not correspond to the polarity set at the inverter. Corrective measures: • Check polarity of SMA Plug-in Grounding.
Page 49
Communication disturbed A fault has occurred in the internal communication of the inverter. However, the inverter continues feeding into the grid. Corrective measures: • Check communications module • If this event occurs often, contact the SMA Serviceline (see section 4 "Contact", page 53). Input A defective String A defective Corrective measures: •...
Page 50
Display text Description Data storage not possible Internal device fault: however, the inverter continues to feed Corrective measures: • If this fault occurs often, contact the SMA Serviceline (see section 4 "Contact", page 53). Update main CPU failed Internal device fault Corrective measures: •...
Page 51
Communication disturbed A fault has occurred in the internal communication of the inverter. However, the inverter continues feeding into the grid. Corrective measures: • If this event occurs often, contact the SMA Serviceline (see section 4 "Contact", page 53). Changing of grid Cause: parameters not possible •...
Page 52
Description General fault General error message Corrective measures: • Contact the SMA Serviceline (see section 4 "Contact", page 53). 10101 Setting of parameter … failed Setting of scalar parameter failed 10102 Parameter … set successfully Status parameter set successfully 10103 Setting of parameter … failed Setting of status parameter failed 10104 Parameter …...