SAFETY
FOR LIFE
To P15
To P12
Ty-Rap*
Cabinet Side View
Figure 5.
Securing with Ty-wraps.
TABLE 2
Troubleshooting Information
Problem
Possible Causes
No power to control. Neon lamp on power supply should be "ON". Connect power.
Display Will
Not Turn
Cable to power supply P12 not connected.
On
Cables incorrectly attached or damaged.
Battery left connected without 120 Vac supplied to control.
Malfunction
Display ON
Battery drained.
and Check
Battery disconnected.
Battery
Display ON
Cables incorrectly attached or damaged.
Incorrect program parameters.
Unit Failed
KMET
Cables incorrectly attached or damaged.
Testing
Cable socket pins bent.
* S280-77-4 Kyle
®
Form 4C Microprocessor-Based Recloser Control Programming Guide
Option I/O
KME4-203
*Tighten to remove
slack in cables
Back Plate
Ref
P7
Grounding Wire
Programming and Testing the
Installed Kit
Note: Follow the testing and programming procedures in
S280-77-1 Kyle Form 4C Microprocessor-Based
Recloser Control Installation and Operation Instructions
before placing the control back in service.
1. Reconnect the battery connector.
2. Energize the control with AC power.
3. Program the control. Refer to S280-77-4 Kyle
4C
Microprocessor-Based
Programming Guide for further information.
4. Test the control with the Kyle
Control Tester (or equivalent) to verify proper pro-
gramming and operation
5. After all programming and testing has been success-
fully completed, the control may be reinstalled and
placed into service. Refer to S280-77-1 Kyle Form 4C
Microprocessor-Based Recloser Control Installation
and Operation Instructions.

Troubleshooting

If the front panel fails to operate properly, review the trou-
bleshooting information in Table 2 prior to contacting your
Cooper Power Systems representative.
Remedy
Connect plug.
Inspect all cables.
Contact Cooper Power Systems.
Contact Cooper Power Systems.
Connect battery.
Inspect all cables.
Verify unit was programmed
correctly. Refer to S280-77-4*.
Inspect all cables.
Inspect / straighten pins.
S280-77-13
®
Form
Recloser
Control
®
Type MET Electronic