Data sheet
Actuators for three point control
AMV 25, AMV 35
Description
Ordering
Technical data
DEN-SMT/SI
AMV electric actuators are used with, VRB, VRG,
VF, VL valves with additional adapter (Code No.
065Z0311, not supplied) and VFS 2 valves up to
DN 50 diameter.
Actuators
Supply voltage
Type
(VAC)
AMV 25
230
AMV 25
24
AMV 35
230
AMV 35
24
Type
Power supply
Power consumption
Frequency
Control input
Closing force
Max. stroke
Speed by 50 Hz (60 Hz)
Max. medium temperature
Ambient temperature
Storage and transport temperature
Grade of enclosure
Weight
- marking in accordance with standards
ED.95.R9.02 © Danfoss 03/2014
The actuator automatically adapts its
stroke to valve end positions which reduces
commissioning time. Optional auxiliary switches,
feedback potentiometer and valve stem heater
are available.
The actuator has some special features:
• The advanced design incorporates load
related 'switch-off' to ensure that actuators
and valves are not exposed to overload;
• Digitale feedback end position indication
signal for valve end position is available by
terminal 4 or 5;
• Low weight and robust;
Main data:
• Nominal voltage:
- 24 VAC, 50 Hz/60 Hz
- 230 VAC, 50 Hz/60 Hz
• Control input signal: 3 point
• Force: 450 N
• Stroke: 15 mm
• Speed: 15 s/mm
• Max. medium temperature: 150 °C
• End-position signals
Accessories
Type
Code No.
Additional switch (2×)
Additional switch (2×)
082G3024
and potentiometer (10 kΩ)
082G3023
Additional switch (2×)
082G3021
and potentiometer (1 kΩ)
082G3020
Adapter for VFS 2 valves DN 15-50
(for media temp. over 150 °C)
Stem heater (for valves DN 15-50)
Adapter for valves VRB/VRG/VF/VL (2009)
DN 15-50
* Need to be ordered separately.
AMV 25
V
24 AC, 230 AC; +10 to –15 %
VA
2
Hz
N
1000
mm
s/mm
11 (8,8)
150 (200 - with adapter or mounted horizontally)
°C
kg
Low Voltage Directive 73/23/EEC,
EMC-Directive 2006/95/EEC: EN 60730-1, EN 60730-2-14
Code No.
082H7015
082H7016
082H7017
065Z7548
065B2171
065Z0311*
AMV 35
7
50/60
3-point
600
15
3 (2,4)
0 ... 55
–40 ... 70
IP 54
1,55
1