2.1 Physical Location

Normally, the pool piping layout and the electrical supply will dictate the general location of the Heat Siphon®.
In addition, the following guideline should be adhered to when picking the location:
1. Allow 24 to 36 inches of open area all around the Heat Siphon® for good air circulation and service access.
Avoid any overhangs or structures which could cause exhaust air to recirculate from the top of the unit back
into the sides.
2. Ensure the Heat Siphon® will be level when in place to aid in condensation and rain water drainage. Sand
or a cement slab will provide and inexpensive attractive easy to level mounting base with good drainage.
3. Heat Siphon's noise dampened plastic base pan ensures extremely quiet operation. To further minimize
noise, point the flat side of the unit with Heat Siphon® trademark toward areas people will frequent. The
plastic front panel reduces the already low operating sound level even further in that direction by absorbing
compressor noise which the evaporator side does less effectively.

2.2 Prohibited Locations

DO NOT locate your Heat Siphon in any of the following
places, as the air will be recirculated back to the inlet
and cooled down cycling repeatedly until the efficiency is
degraded and the compressor is overworked. Location in
any of these places will void your warranty:
1. Under a roof overhang
2. Under a deck
3. In a Pool Pump house

2.3 Distance From The Pool

Normally, the pool pump and Heat Siphon® are in-
stalled close together and within 25 feet of the pool. The
Heat Siphon Installation Space Required
for Air Flow & Service Access ALLOW 12 to 24 inches AROUND ALL SIDES
Colder Air Out Top
12"Min
24-36" Service Access
Installer - 17
Installer Section
®
12"Min
Warmer Air In Sides
PREVENT
Air
Recirculation