Menu 2 – Analogue output FSD
4.1.2
•
Press the MENU button to open the menu system.
•
Using the NEXT and PREVIOUS buttons select menu option:
E:2
•
Press ENTER.
•
Using the INCREASE and DECREASE buttons adjust the FSD
to the required level.
•
Press ENTER.
Note: Pressing the MENU button rather than the ENTER
button exits the sensor FSD feature without any change.
•
Press the MENU button to close the menu system.
Note: The Sensor FSD will be displayed on exit while the
MENU key is pressed.
Menu 3 – Set 4 mA output
4.1.3
•
Monitor the current sourced from the analogue output of the
OEM module using a multimeter set to read milliamps.
•
Press the MENU button to open the menu system.
•
Using the NEXT and PREVIOUS buttons select menu option:
E:3
•
Press ENTER.
•
Using the INCREASE and DECREASE buttons adjust the
output to 4mA .
•
Press ENTER.
Note: Pressing the MENU button rather than the ENTER
button exits the 4 mA feature without performing the
calibration.
•
Press the MENU button to close the menu system.
Note: The 4 mA factor will be displayed on exit.
Issue:
1.14
Rev. 1.0
Page 15