Unoccupied Mode
The fan operates in intermittent mode. When there is a cooling demand from any single zone, the
Heatpump controller will activate the fan and the compressor outputs as long as all temperature
limits, delays and other related parameters are respected. Once the demand is satisfied, the fan and
cooling outputs are deactivated within the min. on/off time delays set.
When there is a heating demand from any zone, the Heatpump controller will activate the fan and
the heating outputs as long as all temperature limits, delays and other related parameter are
respected. Once the demand is satisfied, the fan and heating outputs are deactivated within the min.
on/off time delays set.
During the unoccupied period, the Heatpump controller is driven by the highest demand on the
network and will operate the fan and relevant outputs accordingly.