Commissioning, inspection, maintenance
Separating the neutralising system (if installed) from the boiler and
connecting the drain hose
C
A
Fig. 7
1. Separate hose
to the neutralising system from
A
trap
.
B

Checking the neutralising system (if installed)

1. Check the pH value of the condensate downstream
of the neutralising system with a pH test strip.
Replace the granulate if the pH value is < 6.5.
Note
Part no. for pH test strips: 9517 678.
Observe the neutralising system manufacturer's
instructions.
12
B
2. Connect drain hose
2. Reinstall the neutralising system in reverse order.
to the condensate drain of
C
the trap and run to a drainage system.