Interface; Power Supply Interface And Ground; Grounding - Toshiba T300MV2 Instruction Manual

Medium voltage adjustable speed motor drive
Table of Contents

Advertisement

INTERFACE

The interface between the drive system and external devices is divided into two categories: power
supply system and control system.

Power Supply Interface and Ground

The standard power supplies required are the main circuit input of 2400/4160V 3Φ and (optional)
control power supplies of 120V 1Φ and AC480V 3Φ.
The following figure shows a recommended grounding circuit for the related equipment. Grounding
is intended not only for safety but also to reduce noise problems. The control ground bus is mounted on
insulated standoffs. It may be separated from the power ground and run separately to the earth ground with
insulated cable if noise problems are encountered with auxiliary control devices.
Grounding must follow local and national codes by attaching a properly sized ground conductor
to the drive equipment.
Recommended Ground Circuit
Input transformer
Primary
Earth
Ground

Grounding

IF08CZ10 April, 2019
Secondary
Inverter main circuit
Drive Power/Chassis Ground
- 28 -
Speed Sensor
Motor
PLC
Control Ground