Samsung AM053FXMDCH Service Manual page 98

System air conditioner
Hide thumbs Also See for AM053FXMDCH:
Table of Contents

Advertisement

6) 4Way Valve
Inspection item : 4Way Valve of Outdoor Unit.
Error code: None (The resulting report "Undetermined")
Determine the 4Way Valve operation status of the each Outdoor Unit.
If the judgment of 4Way Valve is "Undetermined" : Checking in accordance with the following order.
Commissioning results,
is Valve and Pressure sensor normal?
Is 4Way Valve connector properly connect ?
Is 4Way Valve coil normal?
(Wire breaking, operation impossible, etc.)
Is PCB Output signal normal ?
Replace 4Way Valve Body
(Retry the Automatic Commissioning :
If the continuous "Undetermined" is displayed. )
Complete
Samsung Electronics
Yes
Yes
Yes
Yes
Check Operation & Amount of Refriherant Automatically Checking
No
Check the corresponding Pressure sensor.
No
No
Replace Valve coil
No
Replace PCB
95

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Am060mxmdchAm048fxmdchAm036fxmdch

Table of Contents