Error Due To Refrigerant Leakage. (E-439) / Operation Prohibited Due To Low Pressure. (E-443) - Samsung AM053FXMDCH Service Manual

System air conditioner
Hide thumbs Also See for AM053FXMDCH:
Table of Contents

Advertisement

3-27. Error due to refrigerant leakage. (E-439) / Operation prohibited due to low pressure. (E-443)

Outdoor unit Display
Judgement Method
Cause of problem
Pressure sensor Open/Short error determination method
1) Identifies from when power is supplied or 2 minutes after RESET, and only when set is stopped.
2) An Open/Short error will occur if the input voltage standard range of 0.5V ~ 4.95V is exceeded.
Did the Pressure
sensor connector get disconnected
from the PCB?
refrigerant inside the set?
(Please check by connecting the
manifold gauge to the service
Out of the PCB
pressure sensor terminals, is there
voltage between
pins 3 and 4 5V?
Replace Low Pressure sensor.
66
(High & low pressure sensor Open / Short error occurs and 1kg/cm2 or less)
When start : When the high pressure sensor value(cooling 3.1kg/ cm2 , heating
2.2kg/ cm2 ) is detection continuously for 3 seconds.
Yes
Is there
valve)
Yes
Yes
E-439 / E-443
No
Please re inspect after connecting the
connector to the PCB.
No
Refill refrigerant after vacuum.
No
Replace PCB.