4. System Design
4-2-4. Configuration method and selection criteria of flow rate adjustment device
In this system, a flow rate adjustment device is installed in the secondary side circuit to perform secondary side flow
rate adjustment control by outputting 0 to 10 V from the unit.
* 10-V power supply is not supplied.
The following shows a system configuration example of the flow rate adjustment device and notes on the system
configuration.
The following three system types are recommended as flow rate adjustment devices:
1. System using a three-way valve
2. System using a two-way valve
3. System using an inverter
1. System using a three-way valve
ON/OFF signal
0 to 10 V output
Notes on selection method and system configuration
Notes on pump selection and connection
Calculate the total pump head according to the system at the site and then select a pump capable of outputting
the minimum flow rate of about 3 ℓ/min and maximum flow rate of about 30 ℓ/min with the necessary pump
head for the piping at the site.
When selecting the pump, please note that output at a high flow rate will not occur if the flow rate with the
pump head of the system at the site is low, and output at a low flow rate will not occur if the flow rate is too high.
Be sure to check that the flow rate becomes 20 to 30 ℓ/min at the maximum output during a flow rate
adjustment test run.
* If the flow rate is not within the range of 20 to 30 ℓ/min, select a different pump or adjust the maximum
frequency using an inverter, etc. so that the maximum flow rate of 20 to 30 ℓ/min is achieved.
* To select a proper pump, first select a pump that supports slightly high flow rate, and then adjust the frequency
with an inverter so that the flow rate becomes 20 to 30 ℓ/min at the maximum output.
(In that case, an inverter is necessary to be prepared separately.)
Notes on three-way valve selection and connection
Use a valve that is capable of adjusting the flow rate with a 0 to 10 V input.
Calculate the Cv value and select a valve that supports an appropriate rate.
Select a valve of which the ratio of the maximum flow rate and the minimum flow rate will be at least 1:10.
Place the three-way valve downstream of the pump. Connect one outlet to the heat exchanger.
Connect the other outlet to the lower part of the tank.
Carefully read the instruction manual and use the three-way valve in accordance with the usage procedures.
MEES19K001
Three-way
Pump
valve
Overview of system
This system has a pump provided at the outlet
of the tank and a three-way valve provided
downstream of the pump, and adjusts the flow
rate by controlling the opening and closing of
the three-way valve.
Flow rate
output device
Pump
Wiring
1-3 of CN512 of
connection
control board
places
(ON/OFF output)
Flow rate
adjustment
device
Three-way valve
Sub box
terminal block
No. 10, 11, 12
37