3. Installation
3-1-2. Installation Space Requirements
Provide sufficient space around the unit for effective operation, efficient air movement, and ease of access for maintenance.
1. Single unit installation
(1) When all walls are within their height limits*.
L3
L3
When the distance behind the unit (L2) needs to be small
(2) When one or more walls exceed their height limits*.
When the wall(s) at the front and/or
the right/left exceed(s) their height
limits
h1
L3
L3
L1
Add the dimension that exceeds the height limit (shown as "h1" through "h3" in the figures) to L1, L2, and L3 as
shown in the table below.
When the distance behind the unit (L2) needs to be small
MEES19K001
≤ 500
L2
L1
When the wall at the rear exceeds
its height limit
h3
≤ 500
L3
L2
L1 (Front)
* Height limit
Front/Right/Left
Same height or lower than the overall height of the unit
Rear
500 mm or lower from the unit bottom
Required minimum distance [mm]
L1 (Front)
L2 (Rear)
500
300
h2
500
L2
L3
L1
Required minimum distance [mm]
L2 (Rear)
L3 (Right/Left)
500 + h1
300 + h2
50 + h3
[mm]
L3 (Right/Left)
50
When all walls exceed their height
limits
h3
h1
L3
L3
L1
h2
500
L2
25