Left Switch; Right Switch - Honeywell M6410A Product Data

67.5 lb 300n non-spring return actuators and 1, 1-1/4, 1-1/2 inch npt cartridge globe valves
Table of Contents

Advertisement

Fig. 5. Mounting actuator to valve (M6410A shown).
T6984F
OPEN
CLOSE
24 VAC
0 VAC
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 6. M6410A used with T6984F.
W7751D,F
SUBBASE
TRIAC EQUIVALENT CIRCUIT
1
1
2 3
4 5 6 7
STEM
UP
M6410 SERIES 60
VALVE ACTUATOR
1 TERMINALS 1
AND 3 LOAD
POWER.
Fig. 7. M6410A Actuator used with W7751D,F Controller.
M19626
M6410
OPEN
CLOSE
COMMON
L1
(HOT)
L2
M19616
8 9 10 11 12
STEM
STEM
COM
UP
DOWN
M6410 SERIES 60
VALVE ACTUATOR
PERIPHERAL
HEATER
STEM
COM
DOWN
REHEATER
M19552
M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES
T7984F
SENSOR
CHANGEOVER
INPUT
0 VAC
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS
AND OVERLOAD PROTECTION AS REQUIRED.
Fig. 8. M7410F used with T7984F.
Fig. 9. Electrical installation showing wire colors
Switch Selection (M7410F)
The two built-in selector switches must be set according to the
valve type (two-way or three-way) and the controller output
signal (0 to 10V or 2 to 10V). See Fig. 10.

LEFT SWITCH

1
INLET
100% ...0%
A
0% ... 100%
Fig. 10. Switch selection according to controller output
signal and valve type (two-way or three-way).
5
CHANGEOVER
CONTACT
OUTPUT
INPUT (2-10V)
24 VAC
COMMON
24 VAC
0 VAC
1 = RED = COM ( )
2 = BLUE =
3 = WHITE = 24V
and definitions.

RIGHT SWITCH

100% (10V)
0% (0V)
OUTLET
V5852A, V5862A
(1, 1-1/4, 1-1/2 IN.)
0% (2V)
100% (10V)
AB
B
V5853A, V5863A
M7410
L1
(HOT)
L2
1
M19617
(0/2 ...10V)
M8222
0V ... 10V
INPUT = 0V ... 10V
2V ... 10V
INPUT = 2V ... 10V
M19627
63-2612—05

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

M7410fV5862aV5863a