Operation - Honeywell M6410A Product Data

67.5 lb 300n non-spring return actuators and 1, 1-1/4, 1-1/2 inch npt cartridge globe valves
Table of Contents

Advertisement

M6410A, M7410F ACTUATORS; V5862A, V5863A VALVES
Input Signal Override (M7410F)
To override the controller output signal, connect the input
signal wire with COM (0%) or 24V (100%), see Fig. 11, using
an external relay.
If the temperature falls below a certain point; for example,
32°F (0°C), a relay can switch the 24 Vac to the Y connection
(0 to 10V, 2 to 10V). This opens or closes the valve.
24 V
24 V
Fig. 11. Input signal override for frost protection.

OPERATION

Apply power to the actuator to drive the synchronous motor to
turn a screw spindle that opens or closes the valve. The
actuator is attached to the valve by a hand-tightened coupling
ring and a magnetic coupling that limit the gear assembly
torque and the actuator driving force.
The actuator pushes the center stem of the valve down,
compressing the valve spring and opening the valve. When
the actuator reverses, the valve spring expands, closing the
valve and pushing the center stem up.
The valves are supplied with a threaded plastic protective
cover/manual handle to protect the stem and to allow for
manual operation. Use the protective cover/manual handle to
fill the system during initial installation.
63-2612—05
= 0 / 2 ... 10V
3
2
1
= 0 / 2 ... 10V
3
2
1
M8226B
Turning the protective cover/manual handle:
— Clockwise: pushes the center stem of the valve down,
compressing the valve spring and opening the valve.
— Counterclockwise: allows the spring to expand, pushing the
center stem up and closing the valve.
NOTES:
You can also use the protective cover/handle for
heating/cooling with neither a controller nor
actuator during the building construction phase.
Retain the protective cover. It can be needed for
future manual operation.
Commissioning
A microprocessor within the actuator maintains accurate
control/positioning by recommissioning itself every 24 hours or
whenever power is applied or interrupted. When power is
applied, the actuator drives to 0 and then to its starting
position according to the starting/input signal. The initial
commissioning or 24-hour recommissioning takes between
2.5 and 5 minutes, depending on tholme position of the
actuator.
Valve Flow
TWO-WAY VALVES
In the two-way valves, the direction of flow is always from inlet
port to outlet port as indicated by the arrows on the valve body
(see Fig. 12).
THREE-WAY VALVES
Three-way valves are designed to be used as mixing valves.
This means that port AB is the total flow outlet; port A is the
controlled flow inlet; and port B is the bypass inlet
(see Fig. 13).
OUTLET
Fig. 12. Two-way valve operation block diagram.
AB
A
B
Fig. 13. Three-way valve operation block diagram.
6
INLET
+
OUTLET
+
AB
A
B
INLET
+
M5357A
+
M5358