5.8 A Connecting Method of DC and AC Line
Refer to the [Figure 5-28] for the PV module connection. The lead wire coming from the PV
module is connected to the distribution box. For the structure of the distribution box, refer
to subsection 5.7. For the connection to the distribution box, connect each to the terminals
of the solar energy of PV1+, PV1-, PV2+, and PV2-. On the other hand, connect the
distribution box terminals with the main body terminals (PV1+, PV1-, PV2+, and PV2-) of the
Scalable All in One in proper order. The lead wire thickness is presented shown in the
following Table.
For the connectors (PV1+, PV1-, PV2+, and PV2-) between the distribution box and the All in
One input, the following types of connectors are used (MC4 connector, PV-Stick Photovoltaic
"
connector
PUSH IN
The [Table 5-7] shows the lead wire standard for the PV. The thickness (6mm
wire is recommended for the All in One.
Type
PE
PV (+), (-)

[Figure 5-29: Load Connector (Male) and Grid Connector (Female)]

"
connection).

[Figure 5-28: PV connector (Female) and PV line (Male)]

Area
6 mm
2
6 mm
2
[Table 5-7: Wire Standard]
Insulation
600 V or more
700 V or more
5. Electrical Connections
) of the lead
2
Color code
Green with yellow lines
Black
46