Fault Diagnosis; Approvals; Product Specifications - Pepperl+Fuchs FYQLA1-140R-3 Instruction Manual

Door interrupt system with logic amplifier
Table of Contents

Advertisement

Door Interrupt System with FYQLA1-140R-3 Logic Amplifier

Fault diagnosis

If fault LED flashes and no sensor alignment problem can be found:
Turn off power
Unwire sensors from input terminals
Power up unit
If fault LED begins to flash repeatedly after 2-3 seconds, the system needs to be
replaced. If the fault LEDs do not begin to flash:
Remove power, then wire one sensor (R,W,B,O) connection at a time. Apply
power, waiting 2-3 seconds. Repeat sequence with all sensors until fault
LED begins to flash. This will be the sensor/actuator that is generating
the fault condition. Reevaluate alignment and terminal connections. If no
problem is found, replace the sensor and/or actuator in question

Approvals

UL508

Product specifications

Input specifications
FYQLA1-140R-3
Input devices
Switch voltage input
Typical response time
Power up time
Output specifications
Contact material
Continuous current
Relay type
Inrush current (max)
Maximum switching
characteristics
(Determined acc. to
EN60947-4-1/EN60947-5-1)
External fusing should be added
to protect the application and unit
from unforseen circumstances
20
120 VAC ± 15% <0.25A @ 45 to 65 Hz
(6) dedicated noncontact hall effect door
sensors (50FY41 series)
12 VDC (2 channel, sink/source)
20 ms (switch open to contact open)
3 s
AgCuNi + 0.2 um Au
5 mA to 5 A (N.O. contact)
1 relay output, force guided connection,
normally open contacts
30 A for 20 ms
AC-1: 250 V/5 A (100,000 cycles)
AC-15: 230 V/3 A (150,000 cycles)
DC-1: 24 V/5 A (100,000 cycles)
DC-13: 24 V/1 A /0.1 Hz (100,000 cycles)